Buderus Logamax GB062-24 KDE H V2 Service Manual page 27

Logamax plus gb062 series; gb062-14 series; gb062-24 series; gb062-22 kd series; gb062-24 kd series; gb062-24 kde series; gb062-24 (k) series; gas wallhung boiler
Table of Contents

Advertisement

4C
- Heat exchanger temperature limiter or flue gas temperature limiter has tripped.
- The differential pressure switch does open when the fan runs (after ignition) (only high modulation version).
Step
1.
Is the system water pressure in green
area (1 - 2 bar) ?
2.
Is the circulation pump blocked or
problem voltage supply ?
3.
Are the flue gas temperature limiter
(STB) cables disconnected ?
B Switch off the boiler.
4.
B Remove the flue gas temperature
limiter (STB) connection cables.
B Measure the flue gas temperature
limiter (STB).resistance.
Is there circuit open?
Logamax PLus GB062
Step
yes:
-->2.
B Add or correct the system water pressure.
no:
B Bleed the air in system.
B Make RESET and start the boiler again.
4C ? --> 2.
yes:
B Remove the blockage (turn the pump shaft).
If no result :
B Switch off the boiler and cut the main supply.
B Drain of he water in boiler.
B Check the fuses. if OK, change the circulation pump.
B Refill the system again and bleed the air.
B Switch on the main supply and the boiler.
4C ? --> 3.
no:
--> 3.
B Switch off the boiler.
yes:
B Connect the cables.
B Switch on the boiler.
4C ? --> 4.
no:
--> 4.
B Change the flue gas temperature limiter (STB).
yes:
B Connect the cables.
B Switch on the boiler.
4C ? --> 5.
no:
B Connect the flue gas temperature limiter (STB) cables.
B Switch on the boiler.
--> 5.
4
Fault finding
27