Service menu settings
3.2.2
Menu 2
To call up a service function in this menu:
B Hold down "Back", + and – at the same time until L.1 is
shown on the display.
Service function
8.A
Software version
8.b
Display soft code number
8.C
Display internal status code
8.d
Display internal fault code
8.E
Returning the appliance to its
standard settings
8.F
Ignition test (permanent)
9.A
Permanent operating mode
9.b
Actual fan speed
9.E
Signal turbine delay
(Combi version)
9.F
Heating circuit pump overrun time
A.A
Temperature at flow temperature
sensor
Tab. 4
Menu 2
12
B Press – until L.2 is shown on the display.
B Press OK to make settings in menu 2.
B Press + or – to scroll through the menu's service
functions.
Possible settings/comments/displays
The current software version is displayed.
internal parameter
internal parameter
This service function enables you to reset the appliance to its standard set-
tings.
Setting 00.
• 0 = Off
• 1 = On
This function permanently sets an operating mode.
The following settings are possible:
• 0: Standard operation; the appliance runs according to controller specifi-
cations.
• 1: The appliance runs at minimum output.
• 2: The appliance runs at maximum output.
Default setting : 0.
Actual fan speed in Hz
Through spontaneous pressure change in the water supply, the flow meter
(turbine) can signal that water is being drawn off.
This means the burner starts briefly although no water is drawn off.
The turbine signal delay can be set from 1 to 8. One step corresponds to
0.25 seconds.
Default setting : 4 (0,25 seconds).
The pump overrun time is started by the control system at the end of the
heat demand.
The following settings are possible:
• 1 to 10: overrun time in minutes (steps of 1 minute)
Default setting : 3 minutes.
This service function allows you to display the temperature at the flow tem-
perature sensor.