6.2 Table IIA
Level II Program Values - 962 Single Twin or Triple Parallel Tank Softener or Dealkalizer (P17=0)
Description of
Parameter
Program Values
P1
Day of Week and
Time of day
P2
Time of day to start
regeneration
P3
Hardness of water
P4
Salt amount
P5
Capacity of unit
P6
Refill controller
P7
Brine draw rate
P9
Backwash time
P10
Rinse time
P11
Purge time
P12
Units of measure
P13
Clock mode
P14
Calendar override
P15
Reserve Type
P16
Initial average
usage or fixed
reserve
P17
Operation type
P18
Salt/Capacity
Change Lock Out
P19
Flow Sensor select
P20
K-factor or Pulse
equivalent
P21
Remote
Regeneration
Switch Delay
P22
Factory Use Only
– DO NOT
CHANGE
Note: This programming sheet is for use with controls
manufactured after 09 Aug 2000.
Min.
Range of Values
Increment
(1-7) 1:00 - 12:59
(1 day)
AM or PM
Metric (1-7)
1 minute
0:00 - 23:59
1:00 - 12:59
1
AM or PM
00:00 - 23:59
3-250
1
30-2500
10
5 – 1250
5
2 - 500
2
1-2600
1
0.1-260.0
0.1
2 - 99
1
2 - 99
1
4 - 30
1
7 - 125
1
2 - 19
1
0 - 1
1
0 - 1
1
0 - 30
1
0 - 3
1
0 - 70
1
0 - 2
1
0 - 1
1
0.01 - 255.00
.01
1 - 254
1
Factory
Units of Measure
Value
None
Hour
Minute
None
Hour
Minute
0
Grains per gallon
0
ppm
10
Pounds
4
Kilograms
0
Kilograins
0
Kilograms
0
0
14
Minutes
40
Minutes
4
Minutes
0
0
0
Days
0
30
Percent of Total
capacity
0
0
0
0.01
60
Seconds
99
35
Notes
Range depends on value selected for
P13. For day of week SUN=1, MON=2,
TUE=3, WED=4, THU=5, FRI=6, SAT=7.
This is the left most digit on the display.
Range depends on value selected for
P13 Use only if P15 = 0 or 1
Unit of measure depends on value
selected for P12
Unit of measure and factory value
depends on value selected for P12
Unit of measure depends on value
selected for P12
Selected from chart in Performance Data
Sections, page 57
Selected from chart in Performance Data
Sections, page 58
May be adjusted for application
May be adjusted for application
May be adjusted for application
0 = US, 1 = Metric
0 = 12 hour clock, 1 = 24 hour clock
0 = no calendar override
0=Variable Reserve, 1=Fixed Reserve
2=Variable Reserve with immediate
regeneration , 3=Fixed Reserve with
immediate regeneration
0 = Single or Parallel
0 = none, 1 = Salt /Capacity Change
Locked Out
0 = Magnum IT NHWB, 1 = 1.0" Autotrol
turbine, 2 = 2.0" Autotrol turbine, 3 =
User defined K-factor, 4 = User defined
pulse equivalent, 5 = Magnum IT HWB
Number used for Meter K-factor or Pulse
equivalent
Time remote switch must be active to
start a regeneration.
Do not change