Nordyne 16 SEER series Installation Instructions Manual page 18

Single phase models
Hide thumbs Also See for 16 SEER series:
Table of Contents

Advertisement

Status led
Status led description
POWER
Module has power
(Green LED)
Thermostat demand signal Y
TRIP
is present, but compressor is
(Red LED)
not running
ALERT
Long Run Time
Flash Code 1
Compressor is running
(Yellow LED)
extremely long run cycles
System Pressure Trip
Discharge or suction
ALERT
Flash Code 2
(Yellow LED)
Pressure out of limits
Compressor overloaded
ALERT
Short Cycling / Compressor is
Flash Code 3
running only briefly
(Yellow LED)
ALERT
Flash Code 4
Locked Rotor
(Yellow LED)
ALERT
Flash Code 5
Open Circuit
(Yellow LED)
18
comfort alert trouBleShooting
Supply voltage is present at module terminals
Compressor protector is open
Check for high head pressure
Check compressor supply voltage
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Broken wire or connector is not making contact
Low pressure switch open if present in system
Compressor contactor has failed open
• Low refrigerant charge
• Evaporator blower is not running
— Check blower relay coil and contacts
— Check blower motor capacitor
— Check blower motor for failure or blockage
— Check evaporator blower wiring and connectors
— Check indoor blower control board
— Check thermostat wiring for open circuit
• Evaporator coil is frozen
— Check for low suction pressure
— Check for excessively low thermostat setting
— Check evaporator airflow (coil blockages or return airfilter)
— Check ductwork or registers for blockage
• Faulty metering device
— Check TXV bulb installation (size, location and contact)
— Check if TXV/fixed orifice is stuck closed or defective
• Condenser coil is dirty
• Liquid line restriction (filter drier blocked if present in system)
• Thermostat is malfunctioning
— Solenoid plug not connected
— Y2 not wired at Comfort Alert
— Check thermostat sub-base or wiring for short circuit
— Check thermostat installation (location, level)
• Comfort Alert failure
• High head pressure
— Check high pressure switch if present in system
— Check if system is overcharged with refrigerant
— Check for non-condensable in system
• Condenser coil poor air circulation (dirty, blocked, damaged)
• Condenser fan is not running
— Check fan capacitor
— Check fan wiring and connectors
— Check fan motor for failure or blockage
• Return air duct has substantial leakage
• If low pressure switch present in system, check Flash Code 1 information
• Thermostat demand signal is intermittent
• Low line voltage (contact utility if voltage at disconnect is low)
• Excessive liquid refrigerant in compressor
• Compressor bearings are seized
• Run capacitor has failed
• Low line voltage (contact utitlity if voltage at disconnect is low)
• Check wiring connections
• Excessive liquid refrigerant in compressor
• Compressor bearings are seized
• Measure compressor oil level
• Outdoor unit power disconnect is open
• Compressor circuit breaker or fuse(s) is open
• Compressor contactor has failed open
— Check compressor contactor wiring and connectors
— Check for compressor contactor failure (burned, pitted or open)
— Check wiring and connectors between supply and compressor
— Check for low pilot voltage at compressor contactor coil
— High pressure switch is open and requires manual reset
• Open circuit in compressor supply wiring or connections
• Unusually long compressor protector reset time due to extreme ambient temperature
• Compressor windings are damaged
— Check compressor motor winding resistance
table 3. led diagnostics
Status led troubleshooting information