Installing the module

Delivery check
The MTAC-01 module package contains:
• MTAC-01 module
• grounding stand-off
• panel port adapter
• this manual.
Mounting
WARNING! Follow the safety instructions given in this manual and
in the ACS350 User's Manual [3AFE68462401 (English)].
To mount the MTAC-01 module:
1. If not already off, disconnect the input power from the drive.
After disconnecting the input power, wait for 5 five minutes
before you start working on the drive.
2. Remove the possible control panel or panel cover from the
drive.
3. Remove the grounding screw in the top left corner of the drive's
control panel slot and install the grounding stand-off in its place.
4. Ensure that the panel port adapter is attached to either the
panel port of the drive or the mate part of the MTAC-01 module.
5. Gently and firmly install the MTAC-01 module to the drive's
panel slot directly from the front.
Note: Signal and power connections to the drive are automatically
made through a 6-pin connector.
6. Ground the module by inserting the screw removed from the
drive in the top left corner of the MTAC-01 module. Tighten the
screw.
Installation