ABB MTAC-01 User Manual page 18

Pulse encoder interface module
Table of Contents

Advertisement

18
Open collector (sinking) encoder output
Diagram assumes normal pulse order in Forward
rotation: Pulse A/1 leads as diagrammed on the
right.
For encoders with pulse B/2 leading, change the diagram for these
connections:
• Encoder A/1 and B/2 should be wired to MTAC terminals B and A,
respectively.
SCR
1) Connect the cable shield at the encoder housing, if, and only if, the encoder is
isolated from the motor, and from the ground.
2) Three identical resistors whose size depends on the encoder power supply
V
V
V
V
V
Installation
Encoder
1
2
0
0V V
CC
1)
= V
:
in
out
= 30 V: R
= 2.7...3.0 kohm, 0.5 W
in
L
= 24 V: R
= 1.8...2.2 kohm, 0.5 W
in
L
= 15 V: R
= 1.0...1.5 kohm, 0.5 W
in
L
= 5 V:
R
= 390...470 ohm, 0.125 W
in
L
A/1
B/2
MTAC-01 module
SCR
SCR
V
in
V
out
2)
GND
R
L
GND
A
A
B
B
Z
Z
Encoder
power
supply

Advertisement

Table of Contents
loading