Parameter assignment for SM326; F-DO 10 x DC 24V/2A PP
(6ES7326-2BF10-0AB0)
Figure 6-1
Maximum test time
With the parameter "maximum test time(s)", you determine the time within which the light
and dark tests are to be conducted (in all combinations) for the whole module. After this time
elapses the tests are repeated. Enter 100s if an error is to be detected quickly, or 1000s if an
actuator needs to be cleared.
Response to CPU STOP
If "Keep last valid value" is set for this parameter, the last valid process value 0 or 1 is kept in
events such as an abortion of PROFIsafe communication or STOP of the F CPU.
Load voltage failure diagnostics
This parameter activates the diagnostic message for a load voltage failure to 2L+ and 3L+.
Compendium Part B - Process Safety (V8.2)
Operating Manual, 07/2016, A5E35031794-AB
Configuring S7F/FH hardware
6.4 Setting system parameters for F-signal modules
55