Parameter Assignment For Sm326; Do 10 X Dc 24V/2A (6Es7326-2Bf01-0Ab0) - Siemens SIMATIC PCS 7 Operating Manual

Process control system compendium part b process safety v8.2
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Configuring S7F/FH hardware
6.4 Setting system parameters for F-signal modules
6.4.7
Parameter assignment for SM326; DO 10 x DC 24V/2A
(6ES7326-2BF01-0AB0)
On fail-safe output modules, the required safety class is achieved by injecting test signals.
Deactivating the light test
For the purpose of the test, 1-signals are connected to the output while the output is inactive
(output signal "0"). This setting activates the output briefly (< 1 ms) (= "light period").
The dark test, which the module performs cyclically, is sufficient for SIL 2. This involves
connecting 0 signals to the output while it is active. The output is deactivated briefly (< 1 ms)
("dark period") in order to detect short circuits. In order to detect cross circuits between
outputs, during the dark test various bit patterns are issued one after the other to a group of
outputs (first the left half of the module, then the right half).
For SIL 3, the light test also needs to be performed or the output switched at least once a
day.
54
Compendium Part B - Process Safety (V8.2)
Operating Manual, 07/2016, A5E35031794-AB