Viessmann VITODENS 200-W Installation And Service Instructions Manual page 78

Type b2hb, b2kb, 1.8 to 35 kw wall mounted gas condensing boiler with vitotronic 200, weather-compensated natural gas and lpg version
Table of Contents

Advertisement

Parameter level 2
Solar
(cont.)
"Controller amplification of speed control"
Setting
4 %/K
... %/K
"Min. speed, solar circuit pump"
Setting
10 %
... %
"Max. speed, solar circuit pump"
Setting
75 %
... %
"Interval function, solar circuit pump"
Setting
OFF
ON
"Maximum cylinder temperature"
Setting
60 °C
... °C
"Maximum collector temperature"
Setting
130 °C
... °C
"Stagnation time reduction"
Setting
5 K
... K
78
Explanations
04:4
04:1 to
Controller amplification adjustable from 1 to 10 %/K
04:10
Explanations
05:10
Min. speed of solar circuit pump 10 % of max. speed
05:2 to
Minimum speed of the solar circuit pump adjustable
05:100
from 2 to 100 %
Explanations
06:75
Maximum speed of solar circuit pump 75 % of max.
speed
06:2 to
Maximum speed of solar circuit pump adjustable from
06:100
2 to 100 %
Explanations
07:0
Interval function of the solar circuit pump switched off
07:1
To capture the collector temperature more accurately,
the solar circuit pump periodically starts for a short du-
ration.
Explanations
08:60
Set DHW temperature (maximum cylinder tempera-
ture) 60 °C
08:10 to
Set DHW temperature adjustable from 10 to 90 °C
08:90
Explanations
09:130
Maximum collector temperature (to protect system
components) 130 °C
09:20 to
Maximum collector temperature adjustable from 20 to
09:200
200 °C
Explanations
0A:5
Temperature differential for stagnation time reduction
5 K
Reduction in the speed of the solar circuit pump to
protect system components and heat transfer medi-
um.
0A:0
Stagnation time reduction disabled
0A:1 to
Temperature differential adjustable from 1 to 40 K
0A:40

Hide quick links:

Advertisement

Table of Contents
loading