"Operating mode, internal circulation pump"
Setting
Not speed-controlled
Speed-controlled without flow rate captur-
ing
Speed-controlled with flow rate capturing
"Set speed of internal circulation pump as boiler circuit pump"
Setting
... %
... %
"Current fault status of burner control unit"
Setting
No fault
"CO limiter"
Setting
Learning mode
Sensor monitoring and fault messaging en-
abled
Deactivated
Explanations
30:0
E.g. temporarily for service
30:1
30:2
Automatic recognition
Explanations
31:...
Set speed of the internal circulation pump when oper-
ated as boiler circuit pump in %, specified by the boil-
er coding card
31:0 to
Set speed adjustable from 0 to 100 %
31:100
Explanations
38:0
Status of burner control unit: Operational (no fault)
38: ...
Status of burner control unit: fault (38:
Explanations
49:0
No CO limiter installed.
Must be set if the CO limiter is to be connected and
automatically activated.
49:1
CO limiter with sensor monitoring and fault message
active.
Is set automatically during commissioning if the CO
limiter is connected.
49:2
Connection between Vitotronic and CO limiter deacti-
vated
If the CO limit is exceeded and the CO limiter is ac-
tive:
CO limiter sounds an alarm
Alarm signal is not transmitted to the control unit
The burner is not switched off
No fault message to the control unit
Parameter level 2