Page 1
D2112 Keypad Diagnostics Putting the Keypad into the Diagnostics Mode 1. Lock the D2112's Standby Switch down. 2. Press the 1 key on the Bell Test keypad. 3. Enter your “Installer” passcode. The default Battery Installer passcode is 654321. The default...
Communication Test The Communication Test sends a Test report to the receiver. If the report fails to be acknowledged after all dialing attempts, the D2112 goes into Communications Failure. • Press ( 3 ). The Communication Test times out immediately.
Point Status The Point Status function displays the electrical state of all points. The state of each point is shown with its corresponding light. 1. Press ( 5 ). The lights update every second. Light Point State Normal WINK Open Short 2.
Page 4
Power Supply Status (Cont'd) To enter the Power Supply Status mode, 1. Press ( 7 ). Light 7 winks to let you know that you’re in the Power Supply Status function. …To display Fire Alarm Load 2. Disconnect the battery. 3.
Current Consumption Scale Light Maximum Fire Alarm Load Maximum Normal Supervisory Load When a test indicates an overload condition, the bar graph flashes.
Page 6
…To display the Minimum Battery Voltage After 1 Minute 2. Make sure the battery is connected. 3. Press ( 2 ). The D2112 automatically disconnects AC. The keypad displays the lowest battery voltage during the test, and gives an acknowledge tone after 1 minute.