Connection To A Collective Detector Line - Siemens FDL241-9 Technical Manual

Linear smoke detector
Hide thumbs Also See for FDL241-9:
Table of Contents

Advertisement

Mounting / Installation
5
Electrical connection
5.3.2
58
Building Technologies
Fire Safety
Variant A
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Connect the negative pole of the external alarm indicator to the negative pole
for the external alarm indicator on the detector.
3. Connect the shielding of the connection cable between the external alarm
indicator and detector on the detector side to the positive pole for the external
alarm indicator via an auxiliary terminal DBZ1190-xx.
Variant B
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Leave the negative pole for the external alarm indicator on the detector
unoccupied.
3. Connect each of the two negative poles of the external alarm indicator
separately to both negative poles of the detector line.
The two negative connections of the external alarm indicator are decoupled
externally in the alarm indicator by diodes.
4. Connect the shielding of the detector line with the shielding of the connection
cable to the external alarm indicator with an auxiliary terminal DBZ1190-xx.

Connection to a collective detector line

Connect a control panel-specific end-of-line to the end of the collective detector
line.
007016_i_en_--
2012-09-07