9.3 Piping length / cooling capacity / heating capacity
RAV-363AH8-PE
RAV-463AH8-PE
Cooling Capacity Ratio
Piping Length (m)
Piping length
less than (m)
Model
(RAV-)
363AH8-PE
463AH8-PE
l
The amount of refrigerant put into the outdoor unit at the factory is equivalent to that which fills up 20m length of refrigerant pipe.
l
If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of the pipe
exceeds 20m, add the refrigerant R-22.
l
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed amount of the
replenishment of the refrigerant is shown in the table above.
The permissible amount of refrigerant is the prescribed amount ±50g.
l
For RAV-363AH8-PE and RAV-463AH8-PE, if the length of pipe exceeds 30m the size of pipe at the gas side must be raised one rank
(e.g. OD 19.0 22.2).
The broken line shows in case the piping length is 30m or less.
9.4 Piping length / additional refrigerant volume
Additional amount of refrigerant
at installation site (kg)
20
25
30
35
0.25
0.5
0.75
Filled at
f a ct o ry
0.75
0.25
0.5
50
5
40
45
10
50
1.0
1.25
1.5
3.0
3.15
1.0
1.25
3.6
1.5
3.7
- 18 -
Heating Capacity Ratio
Piping Length (m)
Recharge amount of interchange time (kg)
15
20
25
30
35
3.25
3.4
3.65
3.9
4.15
3.8
3.9
4.15
4.4
4.65
45
50
40
4.4
4.65
4.9
5.15
5.4
4.9