DT900AM Series DUAL TEC
Figure 1
Feet
DT900AM
Printed Circuit Board (PCB)
Meters

LED INDICATORS

LED
Normal
Power Up/Trouble
1
ON
Rapid Flash
Red
Alarm
ON
Rapid Flash
Yellow
Microwave
ON
Rapid Flash
Green
PIR
1
If a Trouble or INFORMER condition LED pattern disappears before being noted, initiate a self test (see Self Test section),
and the sensor will show the last LED pattern stored in the sensor's memory. To clear this display, initiate another self test.
2
The noted LED patterns will only occur when no motion is present in the detection pattern. For additional microwave
and PIR INFORMER mode LED information, see the Troubleshooting section.
NOTE: LED's operate as listed only when the LED's are enabled (see LED Enable section).

RELAY OPERATION

Relay
Normal
Intrusion
Closed
Open
Alarm Relay
Closed
Closed
Trouble Relay
Closed
Closed
Mask Relay
In a Trouble or Mask condition, the Trouble relay or Mask relay (respectively) will latch open until the condition has been
1
cleared. For more information, see the Troubleshooting section.
For information on INFORMER conditions, see the INFORMER Troubleshooting Matrix in the Troubleshooting section.
2

MASK FUNCTION

Normal Anti-Mask Operation
The DT900AM series features an anti-mask function that detects attempts to mask the sensor. The sensor
sends active Infra-Red beams out into the sensor's field-of-view, and monitors for reflections from materials
that will block or cover the sensor. If the sensor registers a mask condition, it will open the mask relay and
rapidly flash the red and green LEDs. To avoid false mask alarms, follow the mounting guidelines shown in
Step 1.
Clearing an Anti-Mask Condition
Visually inspect the sensor, and remove any materials blocking the sensor's view, and the sensor will
normally reset automatically. If the sensor remains in a Mask condition, walk test the sensor to ensure a
maximum detection range, and then cycle the sensor's power to reset it.
LED ENABLE
(Note: TS50131-2-4 Compliant)
The LED's will only be enabled either by installing Jumper J4 or by connecting the Remote LED Enable
terminal as per the table below (see also INPUT 1 & 2 in the Product Specifications section).
INPUT 1
High/Not Connected
Remote LED Enable
LED's Disabled
LED's Enabled

SELF TEST

The sensor will perform a series of self-tests in the following instances:
• On power up
• Automatically every hour during normal operation
• On installer initiation. Self tests can be installer initiated either by momentarily short circuiting the two self
test pads on the PCB (see Figure 1), or by connecting the Remote Self Test terminal, as per the table
below. (See INPUT 1 & 2 in the Product Specifications section.)
INPUT 2
High/Not Connected
Remote Self Test
Normal Operation
Self Test
INFORMER MODE
The INFORMER mode is a useful diagnostic tool for identifying environmental conditions that are liable to
cause installation problems.
The INFORMER circuit counts the number of events registered by both the microwave and PIR technologies,
and uses the resulting ratio to determine if either technology is working properly or is misapplied. Establish
the INFORMER mode using switch S2 (see Step 7).
Mode 1: Set S2 to position 1. In Mode 1, 32 PIR events without a microwave event will cause the unit to go
into PIR INFORMER. 128 microwave events without a PIR event will cause the unit to go into microwave
INFORMER.
Mode 2: Set S2 to position 2. In Mode 2, 16 PIR events without a microwave event will cause the unit to go
into PIR INFORMER. 16 microwave events without a PIR event will cause the unit to go into microwave
INFORMER.
NOTE: The Mode 2 setting is not recommended. Use only if INFORMER indication is required quickly.
Disabled: To disable INFORMER function, set S2 to the open (OFF) position (factory default setting).
When an INFORMER condition occurs, the trouble relay opens, and the LEDs display an INFORMER trouble
code (see the INFORMER Troubleshooting Matrix in the Troubleshooting section).
NOTE: One LED indication does not relate to one PIR or Microwave event.
TROUBLESHOOTING
Problem: All three LED's are flashing rapidly (LED's are enabled), and the Trouble relay is activated.
Explanation: The sensor is in one of the following three conditions:
Power Up: The sensor is still warming up.
Low Voltage: The sensor's supply voltage is too low.
Self Test Failure: The sensor has failed one of its internal tests.
Solution: Wait for at least 90 seconds for the sensor to power up, and then ensure that the power supply is
greater than 8 VDC. If the three LED's are still flashing rapidly, the sensor is faulty and should be replaced.
Problem: The sensor's LED's are not illuminating.
Explanation: The sensor is not set up correctly.
Solution: Check that either the Jumper J4 is fitted or that the Remote LED Enable terminal is connected to
0V, but NOT both at the same time. If only one of these options is selected, and the LED's still do not
illuminate, the sensor is faulty and should be replaced.
Copyright 2006 Honeywell International Inc.
5-051-367-00 Rev A
6
8
10
12
80
120
200
1.8
2.4
3
3.7
24.4
37
61
OPERATION MODE
Mask
Microwave INFORMER
1,2
PIR INFORMER
Rapid Flash
Rapid Flash
Rapid Flash
OFF
Rapid Flash
OFF
Rapid Flash
OFF
Rapid Flash
OPERATION MODE
Trouble
1
Mask
1
PIR/MW INFORMER
Closed
Closed
Closed
Open
Closed
Open
Closed
Open
Closed
NOTE: Do not fit jumper J4 at the same time as the
Low
Remote LED Enable terminal is low, or the LED's will
not illuminate.
NOTE: When a self test error occurs, the Trouble
Low
relay will latch open and all three LED's will flash
rapidly. If the problem persists, refer to the Trouble-
shooting section.
Honeywell, IntelliSense, DUAL TEC and INFORMER are registered trademarks
of Honeywell International Inc.
All right reserved.
Motion Sensor Product Information
®
TROUBLESHOOTING
Problem: The sensor's PIR range is too long or short.
Explanation: Various mounting locations may require fine vertical adjustment (e.g., due to uneven walls
or floors, etc.).
Solution: During the walk-test, if the PIR is short-ranged, turn the Vertical Adjust Screw counterclockwise. If
the PIR is over-ranged, turn the Vertical Adjust Screw clockwise. (See Step 5.)
Problem: A combination of the sensor's LED's are flashing slowly when there is no motion in the detection area.
Explanation: INFORMER mode is selected on the sensor, and there is a potential false alarm source in the
local environment.
Solution: The table below describes two trouble alerts which are reported by the INFORMER circuit. To
use this troubleshooting matrix:
1) Find the trouble alert that describes the condition of the walk-test LEDs (with no motion in the area).
2) Walk-test the sensor, carefully watching the reaction of the diagnostic LEDs.
3) Refer to the Possible Causes column of the matrix for an explanation of the way in which the
diagnostic LEDs reacted to the walk-test.
4) If no environmental sources can be found, initiate a self test. If the sensor fails the self test,
replace the sensor. If not, relocate the sensor and re-test.
Condition of LEDs
with No Motion
PIR
ALARM
MW
(Green)
(Red)
(Yellow)
(Microwave INFORMER)
(PIR INFORMER)
1,2
LED Legend:
= LED is Flashing
Rapidly
DETECTION PATTERNS
Patterns for: DT900AM
24.4 m (80') Range
TOP
VIEW
2
Patterns for: DT906AM
61 m (200') Range
TOP
VIEW
SIDE
VIEW
37 m (120') Range
TOP
VIEW
SIDE
VIEW
PRODUCT SPECIFICATIONS
Range:
DT906AM
200' Mirror - 61 m x 3 m (200' x 10')
120' Mirror - 37 m x 3 m (120' x 10')
DT900AM
24.4 m x 21 m (80' x 69')
Power requirements:
10 - 15 VDC
50 mA (max) at 12 VDC
AC Ripple: 3V peak-to-peak
at nominal 12 VDC
Alarm relay:
Energized Form C
25 VDC, 125 mA
22 ohm series protection resistor
Trouble relay:
De-energized Form B
(Normally closed)
30 VDC, 25mA
Mask relay:
De-energized Form B
(Normally closed)
30 VDC, 25mA
Tamper Switches:
Wall, top & bottom covers
30 VDC, 25 mA (NC)
INPUT 1 (Remote LED Enable) &
INPUT 2 (Remote Self Test):
Active low (0 to 1.5V)
Inactive high (5 to V+ / Unconnected)
Microwave frequency:
X-Band; 10.687 GHz
PIR white light immunity:
6500 Lux typical
RFI immunity:
30 V/m, 10 MHz - 1000 MHz
Operating temperature:
-10
o
to 55
o
C / 14
o
to 131
(Indoor use environment)
Relative humidity:
5% to 95% relative humidity
(non-condensing)
Please contact your local authorised Honeywell
Made in China
representative for product warranty information.
(Continued)
Reaction of LEDs
to Walk-Test
Type of
Possible
PIR
ALARM
MW
Problem
Causes
(Green)
(Red)
(Yellow)
MW environmental problem
RATIO
MW unstable
IMBALANCE
MW range too long
(Pattern disappears)
PIR was blocked
PIR range too short
RATIO
PIR aimed wrong
IMBALANCE
PIR not reporting
PIR environmental problem
RATIO
PIR unstable
IMBALANCE
MW range too short
(Pattern disappears)
MW range too short
RATIO
MW not reporting
IMBALANCE
= LED is Flashing
Slowly
PIR fields of view:
61 m (200') Range
37 m (120') Range
2 long
6 long
6 intermediate long
4 intermediate long 18 intermediate long
4 intermediate
4 intermediate
4 intermediate lower 8 lower
8 lower
2 down
2 down
Sensitivity:
2 - 4 steps within field-of-view
Dimensions:
20 cm x 16.5 cm x 15.2 cm
8" x 6 1/2" x 6"
Weight:
1.36 kg
Packaged Product Approx.: 1.60 kg
Approvals/listings:
CE
PD6662:2004, prEN 50131-1:2004 and TS50131-2-4:2004
Security Grade 3, Environmental Class II.
Suitable for connection to an EN 60950 Class II Limited Power
Source in European installations.
Note: In TS50131-2-4 compliant installations, mount the
sensor at 2.3 m, select the high sensitivity setting and set
switch S4 to OPEN.
To obtain applicable EU compliance Declaration of Conformities
for this product, please refer to our Website,
http://www.security.honeywell.com/hsce/international/index.html.
For any additional information regarding the compliance of this
product to any EU specific requirements, please contact:
Quality Assurance Department,
Honeywell Security & Custom Electronics,
Newhouse Industrial Estate
Motherwell,
Lanarkshire ML1 5SB,
Scotland,
United Kingdom.
o
F
Tel: +44(0)1698 738200
Email: UK64Sales@Honeywell.com
INFORMER
Troubleshooting
Matrix
NOTE: If on entering the
detection pattern the LEDs
go off, the INFORMER LED
pattern can be retrieved by
initiating a self test. (See
Note 1 in the LED Indica-
tors section.)
=LED is OFF
SIDE VIEW
24.4 m (80') Range
22 long
16 intermediate
12 intermediate lower
8 lower
2 down