Gas Piping - Dunkirk Q90 150 Installation Manual And Operating Instructions

Gas-fired direct vent condensing hot water boiler
Table of Contents

Advertisement

20'
92,000 190,000 350,000 625,000
40'
63,000 130,000 245,000 445,000
60'
50,000 105,000 195,000 365,000
requirements,by the NationalFuel Gas Code,
ANSI Z223.1-latest revision.In Canada,follow
the CAN/CGAB149.1and .2 InstallationCodes
for GasBurningAppliancesand Equipment.
2. Usepipejoint compound suitablefor liquefied
petroleumgason malethreadsonly.
20'
131,000 216,000 189,000 393,000
40'
90,000 145,000 129,000 267,000
60'
72,000 121,000 103,000 217,000
_Jlncludes
Fittings
_80utside Diameter
_obMPORTANT:
length
pipe or tubing should_
The
of
e measured
from the gas meter or propane sec- I
nds!age r egu!a!or:
J
Refer to Figure 12 for the general layout at the boil-
er. The gas line enters
the boiler through
the left
side panel.
GAS PIPING
CONNECTION
The boiler is equipped
with a ½" NPT connection
on
the gas valve for supply piping and ½" NPT ball cock
for manual shut off. The following
rules apply:
3. Use ground joint unions.
4. Install a sediment
trap upstream
of gas con-
trols.
5. Use two pipe wrenches
when making the con-
nection to the gas valve to keep it from turning.
6. Install
a manual
shutoff
valve
in the vertical
pipe about 5 feet above floor outside
the boiler
jacket.
7. Tighten all joints securely.
8. Propane
gas
connections
should
only
be
made by a licensed
propane
installer.
9. Two stage regulation
should
be used by the
propane
installer.
10. Propane
gas piping should
be checked
out
by the propane
installer.
11. It is recomended
to use a ½" union suitable
for natural and propane
gas after the ball cock to
facilitate
service
on the unit.
After all connection
have been made, check imme-
diately
for leaks.
Open
the manual
shutoff
valve.
Test for leaks by applying
soap suds (or a liquid
detergent)
to each joint.
Bubbles
forming
indicate
leak. CORRECT
EVEN
THE SMALLEST
LEAK
AT ONCE.
1. Use only those piping
materials
and joining
methods
listed as acceptable
by the authority
having
jurisdiction,
or in the absence
of such

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q90 175Q90 125Q90 200

Table of Contents