Aluminum series 90+ effecient gas fired boiler water treatment and antifreeze protection

Advertisement

Aluminum
Series
90+
Gas Fired Boiler
Installation
Guidelines,
Water
Treatment
and
Antifreeze
Protection
Z
P/N 240006888
Rev 1.0 [10/07]
IMPORTANT:
These instructions
are in addition to any existing
Antifreeze
and Water Treatment
information
in the boiler instal-
lation manual,
the boilers user's manual
or any other existing
supplemental
instruction
or addendum.
Antifreeze
may be used
in most applications.
Water alone
may also be used in most
applications.
Consult with your heating professional
for recom-
mendations.
The information
in this Supplemental
Instruction
is to be used
in place of that in the following
manuals:
14683301
rev 3.4,
240004826D
rev 1.3, 240006103D
rev 1.1, 14683604
rev 3.4,
240004826K
rev 1.3, 14683450
rev 3.5, 1305016
rev 2.1,
1305016
rev 2.1,240004826B
rev 1.3, 240004826BF
rev 1.3,
240006103B
rev 1.1, 240006103BF
rev 1.0, 1305011
rev 3.4,
240004826U
rev 1.3, 240006103U
rev 1.1.
Recommendations
* System
leaks may not always
be visible. An unseen
system
leak will become
obvious
if boiler pressure
decreases
when
make up valve is closed.
* All system
leaks must be repaired
immediately.
Constant
in-
troduction
of make up water will introduce
dissolved
oxygen,
resulting
in accelerated
boiler corrosion.
Water Chemistrv
L.
* This boiler is designed
for a closed
loop hydronic
heat sys-
tem ONLY! This boiler is not suitable
for natural gravity type
installations,
or any other open type system.
* System fluid pH must be maintained
between
7.0 and 8.0.
* Maintain
water hardness
below 7 grains
hardness.
* Filling
with
chlorinated
fresh
water
should
be acceptable
since drinking
water
chlorine
levels are typically
less than
5 ppm. Do not fill boiler with water
containing
chlorine
in
excess of 100 ppm.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Q90-50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Dunkirk Q90-50

  • Page 1 Aluminum Series Gas Fired Boiler Installation Guidelines, Water Treatment Antifreeze Protection P/N 240006888 Rev 1.0 [10/07] IMPORTANT: These instructions are in addition to any existing Antifreeze and Water Treatment information in the boiler instal- lation manual, the boilers user's manual or any other existing supplemental instruction...
  • Page 2 • Do not inhibitors or other Thoroughly flush system with clean water remove additives that are not specifically approved for this product. any sediment or contaminants. Sludge and iron oxide deposits • Consult a local water treatment can cause rapid breakdown specialist recommendations inhibitors.
  • Page 3 _NOTICE: Antifreeze solutions can • Antifreeze wilt raise the pH of breakdown over time. Failure to the hydronic solution in a heat- check antifreeze chemist_ including system above recom- inhibitors, periodically may result in mended level due to the corro- accelerated corrosion of boiler and sion inhibitors in the antifreeze.
  • Page 4 (Continued) A j2proved Aluminum Antifreeze & Inhibitor Sup.pliers: Approved Product(s): Noble Company Noburst AL Antifreeze PO Box 350 Grand Haven, MI 49417 www.noblecompany.com Tel: 800-878-5788 Fax: 800-272-1519 Approved Product(s): * This product may be used to ad- Rhogard Antifreeeze just the pH level of the hydronic Pro-Tek 922 Inhibitor* system, but on occasion may not resolve the pH issue.