During Operation - Dunkirk Q90 150 Installation Manual And Operating Instructions

Gas-fired direct vent condensing hot water boiler
Table of Contents

Advertisement

SAFETY
SEQUENCES
DURING
OPERATION
DRAFT
INDUCER
TEMPERATURE
SAFETY
SWITCH
IF DRAFT
INDUCER
TEMPERATURE
REACHES
i
TEMPERATURE
SAFETY
SWITCH
SETPOINT,
/
SAFETY
SWITCH
CONTACTS
OPEN
IMMEDIATELY,
I
[
CLOS
NG GAS VALVE_ (L GHT GOES
OUT).
J
[
]
POST
PURGE
AND SWITCHES
OFF.
FOR_HEAT.
rWHEN
TEMPERATURE
SAFETY
SWITCH
CONTACTS
EMAKE
BEFORE
END OF CALL FOR HEAT, CON-
I
[TROL
GOES
NTO NORMAL
L GHT-OFF
SEQUENCE.J
LOSS OF FLAME
SIGNAL
IF AN ESTABLISHED
FLAME
SIGNAL IS LOST WHILE
CONTROL
EXPECTS
THAT THE BURNER
IS OPERAT-
ING, CONTROL
WILL IMMEDIATELY
DE-ENERGIZE
GAS VALVE. VALVE AND FLAME
L GHTS GO OUT.
CONTROL
WILLATTEMPT
TO RELIGHT
BOILER
3 TIMES.
IF FLAME
IS NOT PROVEN,
CONTROL
LOCKOUT
- PROBLEM
ESTABLISHING
A FLAME
SIGNAL.
VALVE
LIGHT
IS BLINKING,
CONTROL
WILL AUTOMATICALLY
RESET
AFTER
1 HOUR.
LOSS
OF COMBUSTION
AIRFLOW
iF COMBUSTION
AIRFLOW
IS LOST WHILE
BURNER
IS FIRING (DIFFERENTIALAIR
PRESSURE
SWITCH
CONTACTS
OPEN)
GAS VALVE WILL BE DE-ENER-
G ZED. VALVE
AND FLAME
L GHTS
GO OUT.
[
!
UTES FOR AIRFLOW
TO BE RE-ESTABLISHED.
IF AIRFLOW
DOES NOT RE-ESTABLISH
CON-
TROL
LOCKOUT
- PROBLEM
WITH COMBUSTION
AIRFLOW.
PURGE
LIGHT
BLINKS.
CONTROL
WILL I
[
AUTOMAT
CALLY
RESETAFTER
15 M NUTES.
J
CASTING
TEMPERATURE
SAFETY
SWITCH
IF BURNER
OPERATES
WHEN BOILER HAS NO WA-
i
/
ER, ALUMINUM
BOILER SECTIONS
HEAT UP RAPIDLY.J
CASTING
TEMPERATURE
SAFETY
SWITCH
CON-
TACTS
WILL
OPEN,
BREAKING
24 VOLT
POWER
TO IBC. POWER
INDICATOR
LIGHT
GOES
OUT.
REQUIRES
MANUAL
RESET
TO RECLOSE
CON-
TACTS.
POWER
LIGHT
GOES
OUT.
HIGH
LIMIT
CONTROL
IF BOILER
WATER
TEMPERATURE
REACHES
i
HIGH
LIMIT (AQUASTAT)
SETPOINT,
HIGH
LIMIT
/
N.C. CONTACTS
OPEN
IMMEDIATELY,
CLOSING
GAS VALVE.
VALVE
AND FLAME
L GHTS
GO OUT.J
DRAFT
INDUCER
CONTINUES
TO RUN FOR 30
|
SECOND
POST PURGE
AND SWITCH
OFF.
!
CIRCULATOR
RUNS AS LONG AS THERMOSTAT
|
CALLS
FOR HEAT.
!
WHEN
HIGH LIMIT
CONTACTS
REMAKE
BEFORE]
END OF CALL
FOR HEAT - CONTROL
GOES
INTO
A NORMAL
L GHT-OFF
SEQUENCE.
J
CIRCULATOR
PUMP
CIRCULATOR
WILL BE ENERGIZED
AS LONG AS
THERMOSTAT
CALLS
FOR_HEAT
DUR NG LOCKOUT.]
RECOVERY
FROM
ANY
LOCKOUT
REQUIRES
RESET,
WHICH
CAN BE ACCOMPLISHED
BY:
(A) REMOVING
AND REESTABLISHING
THE
THERMOSTATS
CALL
FOR HEAT OR TURNING
THE SERVICE
SWITCH
OFF AND BACK
ON;
OR (B) WAITING
FOR THE CONTROL
TO
AUTOMATICALLY
RESETAFTER
15 MINUTES
FOR LOSS OF COMBUSTION
AIRFLOW
OR
ONE HOUR
FOR LOSS
OF FLAME.