Supply Cable Fuses - ABB ACSM1 Hardware Manual

Acsm1-04 drive modules
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

Supply cable fuses

Fuses for short circuit protection of the supply cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on the
supply network impedance and the cross-sectional area and length of the supply
cable. See also chapter
Note: Fuses with a higher current rating must not be used.
Drive type
ACSM1-04xx...
-02A5-4
-03A0-4
-04A0-4
-05A0-4
-07A0-4
-09A5-4
-012A-4
-016A-4
-024A-4
-031A-4
-040A-4
-046A-4
-060A-4
-073A-4
-090A-4
*Without mains choke
Planning the electrical
IEC fuse
Input
current
Rated
(A)
current
Voltage
(A)
(V)
3.2*
6
500
4.7*
6
500
5.7*
10
500
7.8*
10
500
9.8*
16
500
12*
16
500
15*
20
500
20*
25
500
20
25
500
27
32
500
33
40
500
39
50
500
55
63
500
65
80
500
78
100
500
installation.
UL fuse
Rated
Class
current
Voltage
(A)
(V)
gG
6
600
gG
6
600
gG
10
600
gG
10
600
gG
15
600
gG
15
600
gG
20
600
gG
25
600
gG
25
600
gG
35
600
gG
45
600
gG
50
600
gG
70
600
gG
80
600
gG
100
600
Cross-sectional
area of cable
UL
2
mm
AWG
Class
T
1.5 ... 4
16...12
T
1.5 ... 4
16...12
T
1.5 ... 4
16...12
T
1.5 ... 4
16...12
T
1.5 ... 4
16...12
T
1.5 ... 10
16...8
T
1.5 ... 10
16...8
T
1.5 ... 10
16...8
T
6...35
9...2
T
6...35
9...2
T
6...35
9...2
T
6...35
9...2
T
10...70
6 ... 2/0
T
10...70
6 ... 2/0
T
10...70
6 ... 2/0
PDM-00425726
Technical data
75

Advertisement

Table of Contents
loading