Chopper Data / Resistor Selection Table - ABB ACSM1 Hardware Manual

Acsm1-04 drive modules
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

92
• The braking energy must not exceed the energy dissipation capacity of the
selected resistor
• It is highly recommended that the resistor be protected from thermal overload;
see the section

Chopper data / Resistor selection table

The ratings apply at an ambient temperature of 40°C (104°F).
Drive type
ACSM1-04xx...
-02A5-4
-03A0-4
-04A0-4
-05A0-4
-07A0-4
-09A5-4
-012A-4
-016A-4
-024A-4
-031A-4
-040A-4
-046A-4
-060A-4
-073A-4
-090A-4
P
brcont
P
brmax
R
min
R
P
n
E
pulse
The braking resistors are protected to IP20. Refer to page
sizes and tightening torques for the resistors.
Resistor braking
Contactor protection of drive
Internal braking chopper
P
P
R
brcont
brmax
min
(kW)
(kW)
(ohm)
0.9
1.3
1.8
5.5
120
2.6
2.6
4.8
7.9
80
7.0
14.6
40
9.0
13.2
30.7
20
18.0
22.2
43.9
13
26.4
The internal chopper will withstand this continuous braking power. The braking is considered
continuous if the braking time exceeds 30 seconds.
Maximum braking power of the chopper. The chopper will withstand this braking power for 1
second within every 10 seconds. Note: The listed resistors will withstand this braking power
for 1 second within every 120 seconds.
The minimum allowed resistance of the braking resistor.
Resistance of the listed resistor.
Continuous power (heat) dissipation of the listed resistor when cooled naturally in a vertical
position.
Energy pulse the listed resistor will withstand.
below.
Example braking resistor
Type
JBR-01
(Danotherm CAR 155 D T 414 120R)
JBR-03
(Danotherm CAR 200 D T 415 80R)
JBR-04
(Danotherm CBR-V 210 D T 415 40R)
JBR-05
(Danotherm CBR-V 330 D T 415 20R)
JBR-06
(Danotherm CBR-V 460 D HT 415 13R)
R
P
E
n
(ohm)
(W)
120
105
80
135
40
360
20
570
13
790
PDM-425726
108
for dimensions, wire
pulse
(kJ)
22
40
73
77
132