Mitsubishi Electric RD81DL96 User Manual page 32

Melsec iq-r series high speed data logger module (startup)
Table of Contents

Advertisement

Report function performance specifications
Item
Report
Number of settings
File format
Output data type
Number of units of output data
Creation trigger
Period
Layout file size
Number of saved files
Saved file name
Folder switching timing
2 SPECIFICATIONS
30
2.1 Performance Specifications
Specifications
Up to 64
Excel file (extension: .xls)
• Data inside data logging file
• Current value data
• Creation time
64 layouts per report setting, 65535 cells in total
Trigger condition
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
(Single condition)
compare data to data
• Data conditions (value change)
• Fixed cycle: 1 to 86400 seconds
• Time interval specification: Specify hour/minute/second
• Time specification: Specify month, day, hour, minute, second
• At module startup
• At the data logging file switching
Trigger condition
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
(Compound condition -
compare data to data
OR combine)
• Data conditions (value change)
• Fixed cycle: 1 to 86400 seconds
• Time interval specification: Specify hour/minute/second
• Time specification: Specify month, day, hour, minute, second
• At module startup
• At the data logging file switching
Trigger condition
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
(Compound condition -
compare data to data
AND combine)
Trigger condition
Specify the start condition, terminal condition, and count condition. (Up to 3
(Compound condition -
conditions)
Number of times)
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
compare data to data
• Data conditions (value change)
Trigger condition
Specify the start condition and order (1st condition, 2nd condition, or 3rd
(Compound condition -
condition). (Up to 4 conditions)
Order)
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
compare data to data
• Data conditions (value change)
Specify the applicable period or exclusion period.
• Data condition: Bit ON/OFF, compare data to constant value, compare data to
data
• Date range: Specify the start and end in month and day
• Time range: Specify the start and end in hour, minute, and second
• Day of the week/Week of the month conditions: Specify the day of the week
and week
Maximum 10 MB
1 to 65535
■Simple setting
• Add the name
• Add the date (4-digit year, month, day)
• Add the time (hour, minute, second)
• Add the sequential number
■Detailed setting
• 4-digit year/2-digit year, month, day, day of the week, hour, minute, second
• Device value (two types)
• Sequential number
Condition specification
• Data conditions (comparison): Bit ON/OFF, compare data to constant value,
compare data to data
• Data conditions (value change)
• Fixed cycle: 1 to 86400 seconds
• Time interval specification: Specify hour/minute/second
• Time specification: Specify month, day, hour, minute, second
• At module startup
*1
*2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sw1dnn-rdlutl