1.2 Electrical Parameters

Model
GUD35W/NhA-T
GUD50W/NhA-T
GUD71W/NhA-T
GUD85W/NhA-T
GUD100W/NhA-T
GUD125W/NhA-T
GUD140W/NhA-T
GUD100W/NhA-X
GUD125W/NhA-X
GUD140W/NhA-X
GUD160W/NhA-X
Model
220-240V 1N~50Hz
Indoor unit
208-230V 1N~60Hz
NOTICE
Fuse is located on the main board.
Install a circuit breaker at every power terminal near the units (indoor and outdoor units) with at least 3mm contact gap. The
units must be able to be plugged or unplugged.
Circuit breaker and power cord specifications listed in the above table are determined based on the maximum power input of
the units.
Specifications of power cords listed in the above table are applicable in a working condition where ambient temperature is 40℃
and multi-core copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath) is protected by a conduit, and is
resistant to 90℃ in maximum (See IEC 60364-5-52). If working condition changes, please adjust the specifications according
to national standards.
Specifications of circuit breaker are based on a working condition where the working temperature is 40℃. If working condition
changes, please adjust the specifications according to national standards.
Adopt 2pc of 0.75mm² power cords to be the communication cords between indoor and outdoor units. The maximum length is
100m. Please select a proper length according to local conditions. Communication cords must not be twisted together. To be in
compliance with EN 55014, it is necessary to use 8 meters long wire.
Adopt 2pc of 0.75mm² power cords to be the communication cords between wired control and indoor unit. The maximum
length is 30m. Please select a proper length according to local conditions. Communication cords must not be twisted together.
To be in compliance with EN 55014, it is necessary to use 7.5 meters long wire.
The wire gauge of communication cord should not be less than 0.75mm². It's recommended to use 0.75mm² power cords as
the communication cords.
Power supply
V/Ph/Hz
220-240V 1N~50Hz
208-230V 1N~60Hz
380-415V 3N~50Hz/60Hz
Power Supply
V/Ph/Hz
U-Match 5 SERIES UNIT SERVICE MANUAL
Circuit Breaker
Fuse Capacity
A
3.15
8
Circuit breaker
Min. sectional area of
capacity
A
16
16
20
25
32
32
40
16
16
16
16
Min. Sectional Area of
Capacity
Power Cord
A
6
power cord
2
mm
1.5
1.5
2.5
2.5
4.0
4.0
6.0
1.5
1.5
1.5
1.5
2
mm
1.0