9
Diagnostics & error management
9.8
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error ID
Bit15
14
8-bit value (0 ... 255) for error identification within the error subject area.
Tip!
All possible 16-bit error numbers are listed in the table entitled
second column.
9.8.3
Reset error message
An error message with the response "Fault", "Trouble", or "Warning locked" must be explicitly reset
(acknowledged) after the cause of the error has been eliminated.
There are several options to reset (acknowledge) a pending error message:
• Execute the "reset error" device command: Set
• Set the bFailReset control input to TRUE
• In the Lenze setting of C00701/2, this input is connected to the digital input RFR (controller
enable) so that a possibly existing error message is reset together with the controller enable
(if the cause for the fault is eliminated).
• "ResetFault" command via fieldbus: Set bit 7 = "1" in the control word
• When an online connection to the inverter has been established, change to the Diagnostics tab
of the »Engineer« and click the Reset error message button.
Lenze · 8400 motec · Reference manual · DMS 8.1 EN · 02/2018 · TD23
8
7
0
( 330)
"Short overview
C00002/19
= "1"
(A-Z)" in the
329