P0711 – DEVICENET READING #3
P0712 – DEVICENET READING #4
P0713 – DEVICENET READING #5
P0714 – DEVICENET READING #6
Range:
0 to 1199
Properties:
CFG, CAN
Access groups via HMI:
Description:
These parameters allow the user to program the content of input words 3 to 6 (input: slave sends to the
master). Using these parameters, it is possible to program the number of other parameter whose content shall
be made available in the input area of the network master.
For instance, in case it is necessary to read the motor current in amperes from the inverter, the value 3 must be
programmed in some of these parameters, since the parameter P0003 is the parameter that contains this
information. Note that the reading value of any parameter is represented with a 16-bit word. Even if the
parameter has a decimal resolution value, the value is transferred with no decimal indication. For instance, if the
parameter P0003 has the value 4.7, the value transferred via network will be 47.
These parameters are used only if the drive is programmed in parameter P0710 to use options 3 through 6.
According to the selected option, it will be available up to six words for reading by the network master.
The first two input words are fixed.
NOTE!
The 0 (zero) value disables the word writing. The amount of input words, however, always remains the
same as it was programmed in parameter P0710.
P0715 – DEVICENET WRITING #3
P0716 – DEVICENET WRITING #4
P0717 – DEVICENET WRITING #5
P0718 – DEVICENET WRITING #6
Range:
0 to 1199
Properties:
CFG, CAN
Access groups via HMI:
Description:
These parameters allow the user to program the content of output words 3 to 6 (output: masters sends to the
slave). Using these parameters, it is possible to program the number of other parameter whose content shall be
made available in the output area of the network master.
For instance, in case it is necessary to write the acceleration in the inverter, the value 100 must be programmed
in some of these parameters, since the parameter P0100 is the parameter where this information is
programmed. Note that the written value of any parameter is represented with a 16-bit word. Even if the
parameter has a decimal resolution value, the value is transferred with no decimal indication. For instance, if you
want to set the parameter P0100 with the value 5.0s, the value 50 should be written via network.
These parameters are used only if the drive is programmed in parameter P0710 to use options 3 through 6.
According to the selected option, it will be available up to six words for writing by the network master.
The first two output words are fixed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
NET
NET
Default: 0 (disabled)
Default: 0 (disabled)