Minor Fault
506
515
DEV
Speed Deviation
Possible Cause(s):
Corrective Action:
Check the load on the motor, verify the program settings (F1-10 PG
Deviate Level, F1-11 PG Deviate Time. F1-04 PG Deviation Select.
506
515
CE
Memobus Com Err
Possible Cause(s):
Connection is broken, master has stopped communicating.
Corrective Action:
Check all connections, verify all user side software configurations.
Fault Codes
- Operation continues and the digital operator indication blinks
The fault relay does not activate.
505
The deviation of the speed reference and speed
feedback has exceeded the regulation level.
N/A
A minor fault contact output can be programmed by
using the multi-function outputs.
The load has changed considerably.
505
Transmission error. Control data was not received
ce
normally when the power supply is turned on.
Response may be selected.