GE Multilin 3 Series Manual page 48

Retrofits from m & mii family, 239, 735/737, mlj, & tov relays
Table of Contents

Advertisement

M AND MII FAMILY RELAYS
Note
42
8.
From the back of the relay, secure the relay with the new 3 Series screws and M4
Din9021 zinc plated washers (not included) with a torque of 18 in/lb.
The M and MII screws cannot be reused for the 3 Series relay installation, as they are a
different size.
9.
Wire the 3 Series relay, referring to the table provided in Chapter 4: Electrical
Installation, and to the complete product instruction manual if needed.
10. Load the converted settings file if applicable, as described in 2.4 Loading setpoints
from a file.