GE Multilin 3 Series Manual page 41

Retrofits from m & mii family, 239, 735/737, mlj, & tov relays
Table of Contents

Advertisement

CHAPTER 3: INSTALLING THE 3 SERIES RELAY
Φ
0.200"
(5.1 mm)
3 SERIES RETROFIT – INSTRUCTION MANUAL
5.350" 0.010"
±
(135.9 mm 0.25mm)
±
4.100" 0.010"
±
(104.1 mm 0.25 mm)
±
L
C
The panel cutout used to mount the 3 Series relays is the same for the 350, 345, and 339
models. Eight screws are used to mount the relay from the back of the cutout panel.
Depth reducing collars are available in two widths as accessories:
18L0-0076 3 Series depth reducing collar - 1.375" (34.92 mm)
18L0-0075 3 Series depth reducing collar - 3.00" (76.20 mm)
Straight terminal block connectors are available for the non-drawout (NDO) 3 Series relays,
providing screws parallel to the wires for easier access when space is limited.
3S-NDO-STCONKIT 3 Series NDO straight terminal block kit
3 SERIES DIMENSIONS AND MOUNTING
Figure 3-2: 3 Series panel cutout
L
(152.4 mm 0.25 mm)
C
4.000" 0.010"
±
(101.6 mm 0.25 mm)
±
6.900" 0.010"
±
(175.3 mm 0.25 mm)
±
6.000" 0.010"
±
±
35