Assign And Configure An Analog Channel - Raco Catalyst Owner's Manual

Ethernet module setup
Hide thumbs Also See for Catalyst:
Table of Contents

Advertisement

same as when setting a physical address. Refer to the Catalyst manual for that
process.
6. At this point the Catalyst is fully configured to send an alarm on channel 56 if
communication between the PLC and Catalyst is lost.
Let's also set a general alarm, for this example on Channel 5, SNA 1*2*00003.
Simply change the Channel Number and the SNA to the new values and Click
Change Mode. The Catalyst will save and update the settings immediately.
NOTE:
Since the Discrete SNA 1*2*00003 uses one of the bits in the 16bit
Analog register at SNA 1*2*40001, that register cannot be used to store analog
data. Refer to Section C: SNA Discrete and Analog Register Addressing for
more information.
7. Repeat these steps to add additional alarms. When you have finished adding
alarms, Click Close to exit the Channel Settings window.

Assign and Configure an Analog Channel

1. From the PC's Start Menu, start Alarmware v2.0 and connect to the attached
Catalyst.
2. In Alarmware, Click on Configuration > Channels, Enter the desired Channel
number and a SNA in the 4xxxx range (Ch. 2 and 1*2*40005 in this example)
Saved: 2015-08-03
Filename:
Catalyst EtherNet Option Setup R5 V01.docx
RACO Manufacturing and Engineering
Copyright © 1998-2015 RACO. All rights reserved.
Page 20 (37)