6. It is highly recommended that the Catalyst and PLC be assigned static IP
addresses to avoid loss of connectivity if the DHCP server assigns a different IP
than the system was configured to use.
7. For a static IP, enter the IP address, Subnet mask, and Default gateway
provided by your IT Department. You can leave the DNS entries blank.
8. For a Dynamic IP (DHCP) select the DHCP On option button. You do not have
to enter the remaining fields.
9. Close the configuration window and Exit the IPConfig tool.
CAUTION:
If DHCP is left on, the PLC can lose connection with the Catalyst if the
DHCP server changes the Catalyst's IP settings.
B. Test the Catalyst Ethernet Module connectivity
1. Open a browser on the PC and enter in the Catalyst's IP in the address bar.
The browser should display a page similar to this one. If it does not, or if the
Saved: 2015-08-03

Filename:

Catalyst EtherNet Option Setup R5 V01.docx
RACO Manufacturing and Engineering
Copyright © 1998-2015 RACO. All rights reserved.
Page 10 (37)