Contact-type digital displacement sensor / controller

Advertisement

7
BASIC OPERATION
For details on the procedures for operating the product, refer "our web site (http://
panasonic.net/id/pidsx/global)".
● The modes and shortcut functions that can be used from the home screen after
the power is turned ON are as follows.
1. Display switching mode (long press UP key for 2 seconds)
You can change the display of the digital display / SUB (green) as needed for the task.
Normal measured value
Calculated value
Label
2. Teaching mode (long press LEFT key for 2 seconds)
Automatically set HIGH and LOW set values and output HI / GO / LO decision values.
<Example> 1-point teaching
HIGH set value
+0.1000 shift
Measured value (press ENTER key when master workpiece is present)
-0.1000 shift
LOW set value
3. HIGH set value fine adjustment function (short-press UP key)
You can fine adjust the HIGH set value as needed.
4. LOW set value fine adjustment function (short-press DOWN key)
You can fine adjust the LOW set value as needed.
5. Bank mode (long press DOWN key for 2 seconds)
You can write / read the HIGH set value or LOW set value to / from a specified bank (1 to 3).
Bank 1
6. Setting mode (long press RIGHT key for 2 seconds)
You can change basic settings or configure advanced function settings.
Basic settings
Advanced settings
Bank settings
Calibration settings
7. Preset (short-press PRESET key)
You can perform zero-point adjustment, and shift to any preset value.
You can cancel preset by long-pressing the preset key for 2 seconds.
8. Key lock (long press ENTER key + EXIT key for 3 seconds)
You can prevent accidental key operation during measurement.
Key lock setting
8
CAUTIONS
● For the controller DC power supply, only use a power supply that is isolated by
means of an isolation transformer or otherwise.
● Risk of short-circuiting and damage to the controller or power supply if a trans-
former such as an auto transformer is used. Risk of short-circuiting and damage
to the controller or power supply if incorrectly mounted or connected.
● The controller HG-SC□ is designed to be used with the special sensor head HG-S□.
If used with other than the special sensor head option, the specifications will not
be met and product malfunctioning or damage may occur.
● This product has been developed / produced for industrial use only.
● This product uses an EEPROM. The EEPROM has a service life of one million setting operations.
● Do not use this product outside the range of the specifications. Risk of an accident
and product damage. There is also a risk of a noticeable reduction of service life.
● Verify that the supply voltage fluctuations are within the rating.
● If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
● Do not use during the initial transient time after the power supply is switched ON.
● Make sure that the power supply is OFF while performing wiring or connecting a slave unit work.
● Take care that short-circuit of the load or wrong wiring may burn or damage the product.
● After you have completed wiring work, check the wiring carefully before switching
on the power.
● Do not wire in parallel with a high-voltage line or power line, or run through the
same conduit. Risk malfunctioning due to induction.
● Do not apply stress such as excessive bending or pulling to the extracted part of a cable.
● This product is suitable for indoor use only.
● Avoid dust, dirt, and steam.
● Do not use this sensor in places where it may come in contact with corrosive gas, etc.
● Ensure that the product does not come into contact with organic solvents such as thinner.
● Ensure that the product does not come into contact with strong acid or alkaline.
● Ensure that the product does not come into contact with oil or grease.
● This product cannot be used in an environment containing flammable or explosive gases.
● Performance may not be satisfactory in a strong electromagnetic field.
● This product is a precision device. Do not drop or otherwise subject to shock. Risk
of product damage.
● Never attempt to disassemble, repair, or modify the product.
● When the product becomes unusable or unneeded, dispose of the product appro-
priately as industrial waste.
LOW set value
HIGH set value
*When tolerance = 0.1000 (default state)
Bank 2
Bank 3
Calculation settings
Copy settings
Initialization
Maintenance
Key lock activated
Key lock release
9
SPECIFICATIONS
Type
Model No.
Number of connectable units
Supply voltage
Current consumption (Note 2)
Sensor head measured value
Analog current output
(Note 3)
Control output
(Output 1 / Output 2 / Output 3)
Short-circuit protection
Decision output
Alarm output
External input
(Input 1 / Input 2 / Input 3)
Trigger input
Preset input
Reset input
Bank input A / B
Response time
Display resolution
Display range
Protection
Contamination level
Ambient temperature
Ambient humidity
Elevation
Material
Cable
Weight (controller only)
Notes: 1) Measured at a supply voltage of +24V DC and an ambient temperature of +20°C, unless otherwise indicated.
2) Current consumption does not include analog current output.
3) Linearity F.S. = 16mA, and is linearity with respect to digitally measured values. Response time is the time
follwing measured value update.
4) When slave units are connected to the master unit, the maximum sink current / source current of the control
output and ambient temperature vary depending on the number of connected slave units as shown below.
8 to 15 units
5) Do not use or store in an environment pressurized to atmospheric pressure or higher at an altitude of 0m.
10
ERROR DISPLAY
Error Display
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-568-33-7861 FAX: +81-568-33-8591
For sales network, please visit our website.
PRINTED IN JAPAN
Master unit
High performance type
NPN output
HG-SC101
HG-SC111
PNP output
HG-SC101-P
HG-SC111-P
Up to 15 slave units can be connected per master unit.
(When communication unit consolidated: up to 14 slave units)
24V DC ±10%, including 0.5V ripple (P-P)
70mA or less (when sensor head is connected)
• Current output range: 4 to 20mA / F.S.
(default value)
• Error output: 0mA
• Linearity: ±0.25% F.S.
• Load impedance: 250Ω MAX.
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50mA (Note 4)
• Applied voltage: 30V DC or less
(between output and 0V)
• Residual voltage: 1.5V or less
(at 50mA sink current)
• Leakage current: 0.1mA or less
Incorporated (automatic reset type)
NO/NC switching type
Open when alarm
<NPN output type>
Non-contact input or
NPN open-collector transistor
• Input condition
Invalid: +8V to +V DC or open
Valid: 0 to +1.2V DC
• Input impedance: Approx. 10kΩ
Input time 2ms or more (ON)
Input time 20ms or more (ON)
Input time 20ms or more (ON)
Input time 20ms or more (ON)
3ms, 5ms, 10ms, 100ms, 500ms, 1,000ms switching type
-199.9999 to 199.9999mm
-10 to +50°C (No dew condensation or icing allowed) (Note 4), Storage: -20 to +60°C
35 to 85% RH, Storage: 35 to 85% RH
2,000m or less (Note 5)
Case: Polycarbonate, Cover: Polycarbonate, Switches: Polyacetal
2
0.2mm
2-core (brown, blue
0 . 1 5 m m
2
lead wires) / 0.15mm
7-core
composite cable,
composite cable, 2m long
2m long
Approx. 140g
Approx. 140g
Number of connected slave units
Maximum sink current / source
When communica-
current of control output
tion unit consolidated
1 to 7 units
1 to 6 units
7 to 14 units
Description
Both NPN output types and PNP output types
are connected.
Number of connectable units exceeded.
Cannot communicate between controllers.
The calculation function is valid but no slave
units are connected.
The calculation function is valid but an insuffi-
cient number of slave units are connected.
The saved number of connected units does not
match the actual number of connected units.
• Sensor head not connected.
• Broken wire in sensor head connection cable.
• Sensor head failure.
The thrust on the sensor head stroke is above
the specified range.
Unable to preset by external input.
• Failed to write to or read from EEPROM.
• The EEPROM write count is over the ser-
vice life of 1 million.
The detection output load has short-circuited
and excessive current is flowing.
An error has occurred in the internal controller.
© Panasonic Industrial Devices SUNX Co., Ltd. 2016
Slave unit
Standard type
Wire-saving type
HG-SC112
HG-SC113
HG-SC112-P
<PNP output type>
PNP open-collector transistor
• Maximum source current: 50mA (Note 4)
• Applied voltage: 30V DC or less
(between output and +V)
• Residual voltage: 1.5V or less
(at 50mA source current)
• Leakage current: 0.1mA or less
<PNP output type>
Non-contact input or
PNP open-collector transistor
• Input condition
Invalid: 0 to +0.6V DC or open
Valid: +4V to +V DC
• Input impedance: Approx. 10kΩ
0.1μm
IP40 (IEC)
2
2
2
7 - c o r e
0 . 1 5 m m
6 - c o r e
cabtyre cable, 2m
long
Approx. 130g
Approx. 60g
Ambient temperature
20mA
-10 to +45°C
10mA
Action
Connect only units of the same output type.
Connect no more than 15 slave units per master unit.
(When communication unit consolidated: up to 14
slave units)
Switch OFF the power, make sure the controllers are
connected correctly, and then switch ON the power
again.
Change calculation mode to OFF.
Change calculation mode to OFF, or change the cal-
culation application selection setting.
Set the number of connected units check function to
OFF.
• Check if the sensor head is correctly connected.
• Check if there is a broken wire in the sensor head
connection cable. If there is a broken wire in the
sensor head connection cable, replace the cable.
• Replace the sensor head.
Check the sensor head mounting and measurement
object installation position, and adjust so that the
stroke is within the specified range.
Check if the power just been switched on or reset has
just been input, or if a display value is outside the dis-
play upper/lower limit or an alarm has occurred.
• Switch the power OFF then ON, and execute ini-
tialization of the controller from setting mode.
• If the controller does not recover after the above, it
is possible that the EEPROM write count is over
1 million. Replace the controller.
Switch OFF the power and check the load.
Switch the power OFF then ON, and execute initial-
ization of the controller from setting mode.

Advertisement