Table 13: Setscrew Torque Specifications—
Class II Plenum
Fan Size
Setscrew Size
11/12/13
3/8
15
3/8
16
3/8
18
3/8
20
3/8
22
3/8
24
3/8
27
3/8
30
1/2
33
1/2
36
1/2
40
1/2
44
1/2
49
1/2
54
1/2
60
3/4
IM 672-11 • VISION AIR HANDLING UNIT
Torque (ft .-lb)
Aluminum
Steel
19 .2
N/A
19 .2
N/A
19 .2
N/A
19 .2
N/A
19 .2
N/A
19 .2
N/A
19 .2
N/A
19 .2
22
41 .7
55
41 .7
55
41 .7
55
41 .7
55
41 .7
55
41 .7
55
41 .7
55
115
150
Table 14: Bearing Collar and Wheel Hub Set Screw Torque
(All Fans Except Class II Plenum Fans)
Set Screw Diameter (in)
1/4
1/16
3/8
7/16
1/2
5/8
32
o
peraTIon
Minimum torque ft/lbs (kg/m)
5 .5 (0 .76)
10 .5 (1 .45)
19 .0 (2 .63)
29 .0 (4 .01)
42 .0 (5 .81)
92 .0 (12 .72)