Bosch B465 Quick Start Manual page 2

Conettix universal dual path communicator
Hide thumbs Also See for B465:

Advertisement

2.9 | Insert the cellular module (optional)
Insert the cellular module into the slot of the B465 until the
module "clicks" into place. Refer to Figure 2.9.
1
2
MODULE 1
Y
X
MODULE
RELEASE
COMMUNICATION MODULE 1
ETHERNET
100BASE-T
3
LINK
USB
TRBL
SYSTEM TROUBLE
TX
TX
SDI2
RX
RX
POWER
PWR
Device Bus
R Y G B
BATTERY
BAT
INPUTS
2.2 k
End of
24 VDC
Line Resistors
or
16.5 VAC
1 COM 2
3 COM 4
PANEL
PANEL
BATTERY
LINE 1
LINE 2
16.5VAC
+ BAT -
NC
C
NO
C
NO
C
NO
12V
1
COM
2
3
COM
4
T
R
PNL LINE 2
T
R
RELAY 1
RELAY 2
RELAY 3
AUX COM
PNL LINE 1
Figure 2.9: Insert the cellular communication module
Callout ― Description
Callout ― Description
1 ― B44x cellular module
3 ― B465
2 ― Antenna
2.10 | Wire to the control panel
Refer to the enclosure wiring label supplied with the B465, or
the B465 Installation and Operation Guide for specific wire routing
information. Refer to Figure 2.10 for basic wiring routes.
MODULE 1
Y
X
MODULE
RELEASE
COMMUNICATION MODULE 1
ETHERNET
100BASE-T
1
LINK
USB
SYSTEM TROUBLE
TX
TX
RX
SDI2
POWER
Device Bus
PWR
R Y G B
BATTERY
INPUTS
2.2 k
End of
2
24 VDC
Line Resistors
or
PANEL
PANEL
16.5 VAC
1 COM 2
3 COM 4
BATTERY
LINE 1
LINE 2
3
+
-
T
R
T
R
16.5VAC
NC C NO
C
NO
C
NO
12V
1
COM
2
3
COM
4
BATTERY
RELAY 1
RELAY 2
RELAY 3
AUX COM
PNL LINE 1
PNL LINE 2
+ _
10
9
8
7
6
5
4
Figure 2.10: System wiring
Callout ― Description
Callout ― Description
1 ― RJ 45 Ethernet
6 ― 12V AUX/COM terminals
connection to central station
(optional output power source,
Special Application 9.9 - 13.8 V)
2 ― External Annunciator
7 ― Programmable output relays
(Relay 1, Relay 2, Relay 3)
terminal (connected to B46)
3 ― To tamper switch
8 ― Battery (7-18 Ah)
4 ― Phone Line 1/2 to control
9 ― To earth ground
panel terminals
16.5 VAC or 24 VDC power
5 ― EOL input loop
10 ―
supply input terminals
2.11 | Earth ground wiring
Connect the system to earth ground before making other
connections. Doing so prevents damage from electrostatic
discharges or other transient electrical surges. Use a
recommended earth ground reference such as a grounding
rod, or a cold water pipe. Make the connection using 14
AWG (1.8 mm) to 16 AWG (1.5 mm) wire. Refer to the B465
Installation and Operation Guide (P/N: F01U311207).
NOTICE!
The D8004 is required for any Commercial Fire
installations that use a plug-in transformer.
2.12 | Wire to the control panel
Use supporting wiring when connecting a B465 to a intrusion/
fire control panel in order to establish communication. Refer to
Figure 2.11.
3
1
RX
AC
BATTERY
INPUTS
2.2 k
End of
Line Resistors
PANEL
PANEL
1 COM 2
3 COM 4
LINE 1
LINE 2
1
COM
2
3
COM
4
PNL LINE 1
PNL LINE 2
2
T
R
T
R
Figure 2.11: System wiring
Callout ― Description
Callout ― Description
1 ― B465 module
3 ― Intrusion/Fire control panel
2 ― Phone wiring connection
2.13 | Wire to B46 (optional)
Use supporting B46 cable to connect to the B465. Refer to
Figure 2.12.
1
2
MODULE 1
Y
X
MODULE
RELEASE
COMMUNICATION MODULE 1
ETHERNET
100BASE-T
LINK
USB
SYSTEM TROUBLE
3
TX
TX
RX
SDI2
POWER
PWR
Device Bus
R Y G B
BATTERY
INPUTS
2.2 k
End of
24 VDC
Line Resistors
or
PANEL
PANEL
16.5 VAC
BATTERY
1 COM 2
3 COM 4
LINE 1
LINE 2
+
-
C
NO
12V
1
COM
2
3
COM
4
T
R
T
R
16.5VAC
NC C NO
C
NO
BATTERY
RELAY 1
RELAY 2
RELAY 3
AUX COM
PNL LINE 1
PNL LINE 2
Figure 2.12: B46 wiring
Callout ― Description
Callout ― Description
1 ― B465 module
3 ― B46 wiring harness (P/N:
F01U310747)
2 ― B46 module
3 | Configuration
You can configure the B465 using USB. For information on
configuring the B465, refer to the B465 Installation and Operation
Guide (P/N: F01U311207).
4 | LED descriptions
The B465 and B46 modules include on-board LEDs to assist
with troubleshooting issues as well as communication status.
For detailed information on all LED descriptions, refer to the
B465 Installation and Operation Guide (P/N: F01U311207).
7 | Certifications
Region
Certification
US
FCC Part 15 Class B
NIST FIPS 197 AES Certification (IP Communications)
California State Fire Marshall (CSFM)
UL 365 – Police Station Connected Burglar Alarm Units and
Systems
UL 609 – Local Burglar Alarm Units and Systems
UL 864 – Control Units and Accessories for Fire Alarm Systems
UL 985 – Household Fire Warning System Units
UL 1023 – Household Burglar Alarm System Units
UL 1076 – Proprietary Burglar Alarm Units and Systems
UL 1610 – Central Station Burglar Alarm Units
Canada
CAN/ULC S303 – Local Burglar Alarm Units and Systems
CAN/ULC S304 – Signal Receiving Centre and Premise Alarm
Control Units
ULC - S545 – Residential Fire Warning System Control Units
ULC – ORD C1023 – Household Burglar Alarm System Units
ULC – ORD C1076 – Proprietary Burglar Alarm Units and Systems
ICES – 003 – Digital Apparatus
8 | Specifications
Dimensions
79 mm x 128 mm x 38 mm (3.11 in x 5.03 in x 1.50 in)
Voltage output
12 VDC nominal (Special application)
(operating)
Standby battery
*Battery input: B465: Idle 150 mA; Alarm 230 mA
current
Alarm: B465 with B440/B441/B442/B443 = 180 mA
requirements
24 VDC input
*24 VDC input: B465: Idle 120 mA; Alarm 160 mA
current
requirements
USB cable
USB cable (Type A to A male-to-male) - not supplied.
Use a Bosch supported cable such as the B99 cable
(F01U278853)
Compatible
D1640, 120 VAC input, 16.5 VAC, 40 VA output Class 2
transformers
plug-in
D1640-CA 120 VAC input, 16.5 VAC, 40 VA output Class
2 plug-in
D1640-120WI, 120 VAC input, 16.5 VAC, 40 VA output
Class 2 wire-in
Compatible
Contact ID
digital dialer
Pulse 3/1, Pulse 4/2
formats
SIA (SIA8, SIA20)
Compatible
D6600/D6100IPv6/D6100i
receivers
Compatible
B10/B10R Medium Control Panel Enclosure
enclosures
B11/B11R Small Control Panel Enclosure
D8103 Enclosure
Compatible
B46 module (must use supporting B46 cable to connect
module
to the B465)
Relative
Up to 93% non-condensing
humidity
Temperature
0° to +49° C (+32° to 120° F)
(operating)
*Refer to the Standby battery requirements and calculations section in the
B465 Installation and Operation Guide for the current draw requirements of
other system components
Copyright
Use the serial number located on the product label and refer to the Bosch Security
Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Trademarks
All hardware and software product names used in this document are likely to be registered
trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security
Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Conettix Universal Dual Path
Communictor
B465
en Quick Start Guide