Venting Arrangements - Horizontal Terminations - Regency Zero Clearance Direct Vent Gas Fireplace P36-LP4 Specifications

Zero clearance direct vent gas fireplace
Hide thumbs Also See for Zero Clearance Direct Vent Gas Fireplace P36-LP4:
Table of Contents

Advertisement

30
28
26
P36 - P36D Gas Fireplace
Venting Arrangements - Horizontal
24
Terminations
22
This diagram shows all allowable combinations of vertical runs with
horizontal terminations, using one 90º elbow (two 45º elbows equal
one 90º elbow).
20
The lightly shaded area,
18
combinations when installing a P36
The darker shaded area,
, in the diagram shows additional allowable
16
combinations when installing a P36D.
14
12
18
10
16
8
6
14
4
12
2
10
0
8
6
4
2
0
40
, in the diagram shows allowable
0
2
4
6
40-1/2"
(1029mm)
Minimum
Height
Requirement
Gas Fireplaces
Note: Must use optional fl ue adapter (Part # 510-994) when using
Rigid Pipe.
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
Firestops are required at each fl oor level and whenever passing
through a wall.
A vent guard may be required as per local codes, refer to page 11 for
"Exterior Vent Termination Locations".
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
Horizontal (Feet)
8
10
12
P36D ONLY
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
June 2007 Regency Product Specifi cations Book
14
16
18
20

Advertisement

Table of Contents
loading

This manual is also suitable for:

P36-ng4P36d-lp1P36d-ng1