10. Programming Examples

To make circuit 1 an alarm circuit and isolate permit, proceed as follows:
Press key 4 followed by key 1. Whilst in program mode clear all previous configurations.
Press key 1 followed by key 6 (LED's 1 and tamper are on). Press * key to exit.
To make circuit 2 an alarm circuit with walk through (entry route) and isolate permit, proceed
as follows:
Press key 4 followed by key 2. Clear previous configuration. Press key 1 followed by key 4,
then key 6 (LED's 1, 4 and tamper will be o n ). Press * key to exit.
To make circuit 3 a final exit point (door) with chime proceed as follows.
Press key 4 then key 3. Clear previous configuration. Press key 2 followed by key 5 (LED's 2
and 5 are on). Press * key to exit.
To make circuit 4 a part set isolated circuit with walk through (entry route) in full set and
isolate permit, proceed as follows.
Press 4 key followed by the 4 key. Clear previous configuration. Press the 1 key followed by
the 3 key, 4 key and 6 key (LED's 1, 3, 4 and 6 will be on). Press * to exit.
To make circuit 5 a 24 hr or Fire or PA circuit proceed as follows.
Press 4 key followed by the 5 key. Clear previous configuration. Press the 4 key for 24 hour
or press the 5 key for fire or press the 6 key for PA. LED 4 will be ON for 24 hour or LED 5
will be ON for fire or tamper LED for PAwill be ON. Press the * key to exit.
Engineer Access Code
The engineer access code on all new systems is 7 8 9 0. In order to change the engineer
code proceed as follows.
Enter program mode, 7 8 9 0. Create case tamper. Press 1 key, followed by 1 key. LED's 2,
3, 5 and tamper are on. Enter new 4 digit code. With each key pressed an LED will
extinguish. If new code is accepted an accept tone will be generated.
Note : If there is no accept tone the old code will still be valid.
11. Exit Time
The engineer must set the exit time as follows.
From the program mode press the '3' key followed by the '0' key. The time is programmable
from 5 - 105 seconds. Add the displayed number and multiply by 5 e.g. to set for 60 seconds,
press the 6 key followed by the 4 key then the 2 key (LED's 2, 4, and tamper on). Time set is
6 + 4 + 2 = 12 multiplied by 5 = 60 seconds. Press the * key to exit.
Entry Time
The engineer must set the entry time as follows.
From program mode press the '3' key followed by the '1' key. The time is programmable from
5 - 105 seconds. Add the displayed number and multiply by 5 e.g. to set for 40 seconds,
press the '5' key followed by the '3' key (LED's 3 and 5 on). Time set is 3 + 5 = 8 multiplied
by
5 = 40 seconds. Press the * key to exit.
Bell Duration
The engineer must set the bell duration as follows. From mode press the '3' key followed by
the '2' key. Bell duration can be programmed for 1 - 21 minutes. Each key represents the
number of minutes programed. e.g. To set for 15 minutes duration press the 6 key followed by
the 5 key then the 4 key. Time is 6 + 5 + 4 = 15 minutes. Press the * key to exit.