g) PIR Latch Line (L+)
A control line is provided for latching detector. This is a low (0V) when 'unset' and high
(12V) when 'set'. It is marked L+ on the main control board.
h) Detector Reset (ID)
A control line is provided for resetting devices which require the removal of power to reset
(e.g. smoke/viper detectors). Power to these devices should come from +12V Aux to
+12V of the device and ID to 0V (Negative) of the device. The ID line pulses off (open
circuit) at the start of the exit condition (half second pulse) and gives a 3 second pulse at
reset.
i) Remote Keyswitch
Two types of remote keyswitch can be connected to the Rascal Super system. One type
in the remote keypad and one type as a separate option connected to the main PCB.
j) Remote Keyswitch (in keypad)
The Rascal Super control panel can be operated from a remote keyswitch. The keyswitch
is mounted in the remote keypad. To install the keyswitch, power down the system (if
powered), remove the cover by the two screws and the clip holding the blanking in
position. When this is complete, remove the nut from the barrel of the keyswitch and fit
the keyswitch in the cover. Check that the arrow on the keyswitch faces upwards when in
the OFF position. Fit the cable onto the the PCB connector - black or green cable to the
bottom. Refit the cover.
k) Stand alone Keyswitch
This is wired to the PG, COMM and OFF connector on the main PCB. This keyswitch
will give off, full set and part set. Protection is provided by the panel going into full set if
the switch is open or the cable out.