9-4. Air conditioner operates, but abnormalities are observed.

9-4-1. Poor cooling.
• Check position of remote control unit.
Cool air from air conditioner reaches
position directly.
• Wide and narrow tubes between
indoor unit and outdoor unit are
insulated.
• Measure temperature of suction and
discharge air of air conditioner.
Check for clogging of air filter.
• Fan speed is set to LOW.
• Review cooling load estimate,
if performance of air conditioner is
normal.
9-4-2. Excessive cooling.
• Set temperature is suitable.
• Remote control unit is placed where
it can detect room temperature
properly.
YES
NO
YES
Temperature
difference
is small.
Temperature difference between
suction and discharge air is
large enough (approx. 10 deg. or more).
Air filter is clogged.
YES
NO
NO
Change position of remote
control unit.
Insulate both wide and narrow
tubes separately and then
tape together.
Possibility of
gas shortage.
Clean filter.
Set fan speed to either
HIGH or MEDIUM.
Reduce cooling load or
replace the air conditioner
with larger capacity.
Set temperature to higher
value using temperature
setting buttons of the remote
control unit.
Change position of remote
control unit.
55
Charge refrigerant
gas (R22).