Sanyo SAP-K161GJA Technical & Service Manual page 37

Split system air conditioner
Table of Contents

Advertisement

Indoor Unit
SAP – K181GJA
Outdoor Unit
SAP – C181GA
Performance at
Rating Conditions
Full Load Conditions Running Amps.
Rating Conditions
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Indoor Unit
SAP – K181GJA
Outdoor Unit
SAP – C181JA
Performance at
Rating Conditions
SSA 385, 386
Conditions
Full Load Conditions Running Amps.
Rating Conditions
SSA 385, 386 Conditions (Saudi standard)
Full Load Conditions : Indoor Air Temperature 29°C D.B. / 19°C W.B.
SAP – K181MBA
SAP – C181MA
Indoor Unit
Running Amps.
A
0.37
Power Input
kW 0.070 / 0.073
A
0.37
Power Input
kW 0.070 / 0.073
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Outdoor Air Temperature 52°C D.B.
SAP – K181MBA
SAP – C181BA
Running Amps.
A
Power Input
kW
Running Amps.
Power Input
A
Power Input
kW
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
: Indoor Air Temperature 29°C D.B. / 19°C W.B.
Outdoor Air Temperature 46°C D.B. / 24°C W.B.
Outdoor Air Temperature 54°C D.B.
Fan Motor
Fan Motor
220 – 240V ~ 50Hz
/ 0.38
0.48 / 0.50
0.105 / 0.119
/ 0.38
0.48 / 0.50
0.105 / 0.119
Indoor Unit
Fan Motor
Fan Motor
220V ~ 60Hz
0.40
0.54
0.079
0.119
0.40
0.54
0.079
0.119
0.40
0.54
0.079
0.119
34
Outdoor Unit
Compressor
8.75
/ 8.62
1.855 / 1.918
13.05 / 12.52
2.785 / 2.838
Outdoor Unit
Compressor
6.87
1.502
8.17
1.792
9.87
2.162
Complete Unit
9.6
/
9.5
2.03
/ 2.11
13.9
/ 13.4
2.96
/ 3.03
Complete Unit
7.8
1.70
9.1
1.99
10.8
2.36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents