Mitsubishi Electric Mr.Slim PMH-P25BA Service Manual page 20

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PMH-P25BA:
Table of Contents

Advertisement

9-6. TEST POINT DIAGRAM
Indoor controller board
PMH-P25BA
PMH-P35BA
PMH-P50BA
FAN
Fan motor output (MF)
Between 1 to 5
220~240V AC
CN03
Connect to the outdoor unit
Between 1 to 3
220~240V AC
+
Between 3 to 5
0~24V DC
CNP
Drain-up machine
output (DP)
Between 1 to 3
220~240V AC
Jumper wire J41, J42
Pair number setting with
wireless remote controller
CN90
CN32
Connect to the wireless
Connector
remote controller board
(Remote switch)
SWE
Emergency
operation
20
CN22
Connect to the terminal block (TB5)
(Remote controller connecting wire)
(10~16V DC)
– +
Jumper wire J11~J15
Jumper wire J21~J24
Model setting
Capacity setting
CN31
Drain sensor (DS)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN29
Condenser/Evaporator
temperature thermistor
(TH5)
CN6V
Vane motor output
(MV)
CN41
Connector
(HA terminal-A)
CN2L
Connector
(LOSSNAY)
CN25
}
Humidifier output
+
(12~16V DC)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr.slim pmh-p50baMr.slim pmh-p35ba

Table of Contents