<Thermistor Characteristic graph>
Room temperature thermistor(TH1)
Thermistor for
Pipe temperature thermistor(TH2)
lower temperature
Condenser/evaporator temperature
thermistor(TH5)
Thermistor R
=15kΩ ± 3%
0
Fixed number of B=3480 ± 2%
1
Rt=15exp { 3480(
273+t
0:
15kΩ
10:
9.6kΩ
20:
6.3kΩ
25:
5.4kΩ
30:
4.3kΩ
40:
3.0kΩ
Thermistor for
drain sensor
Thermistor R
=6.0kΩ ±5%
0
Fixed number of B=3390 ±2%
1
Rt=6exp { 3390(
273+t
0:
6.0kΩ
10:
3.9kΩ
20:
2.6kΩ
25:
2.2kΩ
30:
1.8kΩ
40:
1.3kΩ
1
) }
273
1
) }
273
19
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (:)
< Thermistor for drain sensor >
10
9
8
7
6
5
4
3
2
1
0
-20
0
20
40
Temperature (:)
60
80