Schlage M490DE Installation Instructions And Use page 9

Table of Contents

Advertisement

6d Set SW2 dip switches.
NOTE: Dip switch panel may be upside-down, depending on installation. Look for the "OFF" label and
L
compare to the images below for correct dip switch positions.
Feature
Switch
Nuisance Delay
1
2
Nuisance Alert
3
Auto Relock
4
Anti-Tailgate
5
Door Propped/Forced
6
Unlock Alert
7
DEL Enabled
8
6e Set relock time - SW4.
Relock time is the amount of time
the lock is de-energized after a valid
release. If auto relock is enabled, it
also controls the amount of time the
lock is unlocked before it automatically
relocks after a power-on or fire alarm
reset. Programmable 0-30 seconds in
2 second increments.
Setting
Delay in Seconds
0
0
1
2
2
4
3
6
6f Set door prop time - SW3.
The amount of time the door must be
propped open (after normal release time
delay has ended) before triggering the
alarm. The alarm will clear as soon as the
door closes again. Programmable 0-150
seconds in 10 second increments.
Setting
Delay in Seconds
0
0
1
10
2
20
3
30
Setting
0 seconds
1 second
2 seconds
Off
On
Off
Off
Off
On
Off=Disabled
On=Enabled
Off=Disabled
On=Enabled
Off=Disabled
On=Enabled
Off=Disabled
On=Enabled
Off=Disabled
On=Enabled
Off=Disabled
On=Enabled
Setting
Delay in Seconds
4
8
5
10
6
12
7
14
Setting
Delay in Seconds
4
40
5
50
6
60
7
70
Description
3 seconds
Nuisance delay is the amount of time the door must be pushed or
aux input must be pressed before triggering the Delayed Egress
On
Cycle.
On
Programmable to 0-3 seconds.
Causes horn to sound during nuisance delay
When enabled, lock will energize upon regaining power or after a fire
alarm condition clears.
Door will relock as soon as it closes – even if the relock time delay
has not ended.
Enables door propped and door forced alarms
Horn sounds whenever door is unlocked and power is still applied to
the door
Enables or disables the DEL plunger switch. Aux Input will always
function even if DEL plunger switch is disabled.
Setting
Delay in Seconds
8
16
9
18
A
20
B
22
Setting
Delay in Seconds
8
80
9
90
A
100
B
110
8
Setting
Delay in Seconds
C
24
D
26
E
28
F
30
8
Setting
Delay in Seconds
C
120
D
130
E
140
F
150
9