Toyotomi CCT 140IUINV Service Manual page 72

Refrigerant r-410a
Table of Contents

Advertisement

2.2 Indoor unit malfunction
For floor standing:
Codes
P0
Evaporator low temp. protection
Ed
Outdoor unit malfunction
E1
Indoor / outdoor units communication error
E2
Open or short circuit of T1 temperature sensor
E3
Open or short circuit of T2 temperature sensor
E4
Open or short circuit of T2B temperature sensor
E7
EEPROM chip malfunction
E8
Indoor fan speed is out of control
For the others tyoes:
NO. 
Malfunction 
Communication malfunction between indoor
and outdoor units. 
Open or short circuit of T1 temperature
sensor 
Open or short circuit of T2 temperature
sensor 
Open or short circuit of T2B temperature
sensor 
Full-water malfunction 
Indoor EEPROM malfunction 
Refrigerant Leakage Detection 
Outdoor unit malfunction 
Indoor fan speed is out of control 
Communication malfunction between main
10 
PCB and up-down panel PCB 
11 
Up-down panel malfunction 
12 
Up-down panel is not closed 
Communication malfunction between master
13 
unit and slave unit 
Other malfunction of master unit or slave unit
14 
Notes: Digital display is only available for super-slim 4-way cassette & duct type.
Electrical Control System
Defrosting
lamp  
☆ 
☆ 
☆ 
☆ 
☆ 
☆ 
O (on)
X(off) ☆(flash at 5Hz) ◎(flash at 0.5Hz)
F0,F1,F2 are only available for super-slim 4-way cassette 
Contents
Alarm
Running lamp 
lamp  
☆ 
☆ 
☆ 
☆ 
☆ 
◎ 
☆ 
☆ 
☆ 
☆ 
☆ 
☆ 
☆ 
☆ 
Troubleshooting
Timer
Display(digital
lamp 
tube) 
E1 
☆ 
E2 
E3 
E4 
EE 
E7 
EC
Ed 
E8 
X
F0 
F1 
O
F2 
F3 
F4 
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents