9 Error messages

9.1 LCD Display

The LCD HMI in case of transmitter errors or malfunctioning is capable of displaying specific error/fault messages to help the user
in identifying the problem and resolve it. In case of an alarm, a message consisting of an icon and text appears at the bottom of
the process display. Use the (1) key to call up the information level. Use the "Diagnostics" menu to call up the error description
with a help text. In the error description, the error number is displayed in the second line (M028.018). Two further lines are used to
describe the error. The device status is divided into four groups. The message text beside this icon in the display provides
information about where to look for the error. There are the following areas: Electronic, Sensor, Configuration, Operating and
Process.
Icon
Description
Error / Failure
Functional check (e.g. during simulation )
Out of Spec (e.g. operating with empty meter pipe)
Maintenance required

9.2 Error states and alarms

— Communication Board / Electronic related error messages.
Error message Tx LCD message
F116.023
Electronic Memory Failure
NV Electronic Memory Burn
M026.024
Error
—Sensor related error messages
Error message Tx LCD message
F120.016
Sensor Invalid
F118.017
Sensor Memory Fail Sensor memory corrupted
F114.000
P-dP Sensor Fail
Static Pressure
F112.001
Sensor Fail
Sensor Temperature
F110.002
Fail
NV Sensor Memory
M028.018
Burn Error
—Configuration related error messages.
Error message Tx LCD message Possible cause
Input Simulation
C088.030
Active
Input Simulation
C088.030
Active
Possible cause
Electronic memory corrupted
Writings to the electronic non-
Volatile Memory has not been
successful
Possible cause
The sensor signal is not being updated correctly as a
result of an electronics failure, sensor error or a poorly
connected sensor cable.
Mechanical damage to the sensor. Loss of fill fluid from
the cell, ruptured diaphragm, broken sensor.
The circuitry for the sampling of the static pressure has
failed.
The circuitry for the sampling of the temperature has
failed.
Writings to the sensor non-Volatile Memory was not
successful
The P-dP Value produced in output is
derived by the value simulated in input
The Static Pressure Value produced in
output is derived by the value simulated in
input
Suggested action
The electronic must be replaced
The communication board should be replaced
as soon as possible
Suggested action
Check cable connection,
check sensor and if problem
persists, the sensor must be
replaced.
The sensor must be replaced
The sensor must be replaced
The sensor must be replaced
The sensor must be replaced
The sensor should be replaced
as soon as possible.
Suggested action
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove
the input simulation)
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove
the input simulation)
2600T Series Pressure transmitters | OI/266/LowP-EN Rev.A 23
9 Error messages
Tx response
Analog Signal to Alarm
no effect
Tx response
Analog Signal to
Alarm
Analog Signal to
Alarm
Analog Signal to
Alarm
Analog Signal to
Alarm
Analog Signal to
Alarm
no effect
Tx response
no effect
no effect