Feeder Protection and Control
REF615
Product version: 2.0
Table 55. Arc protection (ARCSARC) main settings
Parameter
Phase start value
(Operating phase current)
Ground start value
(Operating residual current)
Operation mode
Table 56. Operating characteristics
Parameter
Operating curve type
(current protection)
Operating curve type
(voltage protection)
Control functions
Table 57. Autoreclosure (DARREC)
Operation accuracy
36
Function
Value (Range)
ARCSARC
0.50...40.00 x I
ARCSARC
0.05...8.00 x I
ARCSARC
1=Light+current
2=Light only
3=BI controlled
Values (Range)
1=ANSI Ext. inv.
2=ANSI Very. inv.
3=ANSI Norm. inv.
4=ANSI Mod inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
±1.0% of the set value or ±20 ms
1MRS756379 D
Step
0.01
n
0.01
n
ABB