Specifications - Allen-Bradley 1746-BTM Installation Instructions Manual

Barrel temperature control module
Table of Contents

Advertisement

14
Barrel Temperature Control Module

Specifications

Module Location
Input from System Backplane
Thermocouple Types
Input Voltage
Number of Channels
A/D Conversion Method
Input Filtering
Normal mode rejection
between
[+] input and [-] input
Common mode rejection
between inputs and chassis
ground
Channel bandwidth (-3db)
Calibration
Isolation
Operating Temperature
Storage Temperature
Relative Humidity
Required Terminal Block
Wiring
1
Wire Category
Torque
Enclosure Type Rating
2
Certifications
(when product is marked)
User Manual
1
Use this conductor category information for planning conductor routing as described in publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.
2
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Publication 1746-IN020B-EN-P - July 2002
SLC chassis - any I/O module slot except 0
5Vdc @ 0.110 A, 24Vdc @ 0.085A
b, c, d, e, j, k, n, r, s, t
-50 to +50mV and -100 to +100mV
4 (backplane and channel-to-channel isolated)
Sigma-Delta modulation
Analog filter with low-pass digital filter
Greater than 50dB @ 50Hz
Greater than 60dB @ 60Hz
Greater than 120dB @ 50/60 Hz with 1K ohm imbalance
8Hz
Once every six months
Tested to 1000Vac for 60 sec. between channels and between user connections
and backplane connections
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
o
o
0-60
C (32–140
F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
o
o
–40 to 85
C (–40 to 185
F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5–95% non condensing
Cat. No. 1746-RT32
24-14 AWG
2
6-8 in-lbs.
None (open style)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I, Division 2 Group
A,B,C,D Hazardous Locations
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS 2064; Industrial Emissions
Publication 1746-UM010, Barrel Temperature Module User Manual