14
Barrel Temperature Control Module
Specifications
Module Location
Input from System Backplane
Thermocouple Types
Input Voltage
Number of Channels
A/D Conversion Method
Input Filtering
Normal mode rejection
between
[+] input and [-] input
Common mode rejection
between inputs and chassis
ground
Channel bandwidth (-3db)
Calibration
Isolation
Operating Temperature
Storage Temperature
Relative Humidity
Required Terminal Block
Wiring
1
Wire Category
Torque
Enclosure Type Rating
2
Certifications
(when product is marked)
User Manual
1
Use this conductor category information for planning conductor routing as described in publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.
2
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Publication 1746-IN020B-EN-P - July 2002
SLC chassis - any I/O module slot except 0
5Vdc @ 0.110 A, 24Vdc @ 0.085A
b, c, d, e, j, k, n, r, s, t
-50 to +50mV and -100 to +100mV
4 (backplane and channel-to-channel isolated)
Sigma-Delta modulation
Analog filter with low-pass digital filter
Greater than 50dB @ 50Hz
Greater than 60dB @ 60Hz
Greater than 120dB @ 50/60 Hz with 1K ohm imbalance
8Hz
Once every six months
Tested to 1000Vac for 60 sec. between channels and between user connections
and backplane connections
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
o
o
0-60
C (32–140
F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
o
o
–40 to 85
C (–40 to 185
F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5–95% non condensing
Cat. No. 1746-RT32
24-14 AWG
2
6-8 in-lbs.
None (open style)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I, Division 2 Group
A,B,C,D Hazardous Locations
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS 2064; Industrial Emissions
Publication 1746-UM010, Barrel Temperature Module User Manual