Entries For Double-Point Indications - ABB REB500 Communication Protocol Manual

Distributed busbar protection iec 60870-5-103 substation automation products
Hide thumbs Also See for REB500:
Table of Contents

Advertisement

Section 3
IEC 60870-5-103
3.5.4
20
Table 24
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
0
0
0
0
Spontaneous <1>
REB500 CU/BU No.
GEN <254>
Read value of single entry <244>
<0>
{1, 0, 0}
43 H
01 H
Current value <1>
<23>
DATA STRUCTURE
14
1,0
<9> DOUBLE-POINT I
NFORMATION
1
1,0
0
0
0
0
0
<14>
BINARY TIME
7
1,0
Time stamp (CP56Time2a)

Entries for double-point indications

Table 25
Directory entry for GIN 0x4600 (header)
COD
Data type
<10> Description
<1>
<1>Current value
<3> UI
Table 26
Directory entry for GIN 0x4600 (header)
COD
Data type
<10> Description
<1> os8ascii
<1> Current value
<23> data
structure
<9> Double
Point
INFORMATIO
N WITH
TRANSIENT
AND ERROR
<14> binary
time
1
0
Type Identification
0
1
Variable Structure
Qualifier
Cause Of Transmission
Common Address of ASDU
Function type
Information number
Return information identifier
Number of generic data sets
Generic identification
number
Kind of description
DATA TYPE
DATA SIZE
,
NUMBER
CONT
DATA TYPE
DATA SIZE
,
NUMBER
CONT
0
<0 .. 3>
DATA TYPE
DATA SIZE
,
NUMBER
CONT
Length
Num
ber
8
24
1
OS
ASCII
1
1
Length
Num
ber
20
1
14
1
1
1
7
1
Communication Protocol Manual, IEC 60870-5-103
1MRK 511 371-UEN
10
SQ=1, SQ_No.= 1
COT
<0 .. 60>
FUN
INF
RII
NGD {NO, COUNT, CONT}
Group
<41H .. 45H>
Entry
<1 .. 255>
KOD
GDD
GDD 1
GID 1
GDD 2
GID 2
Value / Significance
"Double-point Indications"
Number of DPI defined in this group.
Value / Significance
Event text defined by user
(Includes the following two definitions)
TRANSIENT (0) /
OFF (1) / ON (2) /
ERROR (3)
Time stamp (CP56Time2a)
Distributed busbar protection REB500
DATA UNIT
IDENTIFIER
INFORMATION
OBJECT

Advertisement

Table of Contents
loading