The columns are separated by a semicolon ";". The following is an example of an
export file generated by HMI500:
--------------------------------------------------------------------------------------------------
IEC 60870-5-103 Disturbance Recorder signals
--------------------------------------------------------------------------------------------------
CAA;ABB ref.; Feeder; Station number; Signal ID; Signal text
0;CU;-;Null;Null;Null
2;BU2;BU2;2;1;Trip
2;BU2;BU2;2;2;In service
--------------------------------------------------------------------------------------------------
IEC 60870-5-103 events and private Information Object Identifier settings
--------------------------------------------------------------------------------------------------
CAA;ABB ref.; Feeder; Signal text; IEC FUN;IEC INF
0;CU;BU2;41810_In service;254;18
2;BU1;BU1;23310_BFP trip t2;254;85
2;BU1;BU1;221105_I0INV Trip Si;160;67
2;BU1;BU1;211880_DIST Com Send.2;128;76
Table 13
Description of the columns above
Colum
Description
CAA
Common Address ASDU: Sub-address for
identifying a Bay Unit at the application level
ABB ref.:
ABB's designation for the Bay Unit
Feeder:
User's designation for the respective bay
Station Number:
Disturbance recorder number
Signal ID:
Consecutive signal number
Signal Text:
User's signal description
IEC FUN:
Assigned IEC function type
IEC INF:
Assigned IEC information number
The above Signal Id and Signal Text assignment for a specific Bay Unit can also be
made via HMI500 providing a COMTRADE file for the Bay Unit disturbance
recorder is uploaded. The file <filename>.cfg generated by the PC contains the
same in-formation as the list generated by the export tool.
The assignment can change when the disturbance recorder con-figuration changes,
for example, by deleting or adding signals. The above list then has to be recreated
and possibly corrected by the control system.
The configured length of disturbance records shall not exceed one
second (1s) to avoid conflicts with the maximum number of 65535
Events foreseen in IEC81750-5-103.