Section 2
Interbay bus functions
10
Table 4
SCS Differential Current Parameters
Item
Description
Update period
Determines how often the differential current
measurement has to be updated.
Enabled
Enables polling of the bus zone differential
currents.
Delta L1_L2_L3
Applies to all bus zones. Delta per bus zone for
phases L1, L2 and L3.
Dead band
Dead band per bus zone for phases L1, L2 and
L1_L2_L3
L3.
Delta L0
Delta per bus zone for the neutral current L0.
Dead band L0
Dead Band per bus zone for the neutral current
L0
'Delta' and 'Dead band' settings that are too low result in a high
data load on the bus. For this reason, care should be taken to set
reasonable values.
Min. Max.
0
1000
yes
no
0
65535
0
65535
0
65535
0
65535
Communication Protocol Manual, IEC 60870-5-103
Distributed busbar protection REB500
1MRK 511 371-UEN
Default Step Unit
60
100
s
Yes
10
1
A
5
1
A
10
1
A
5
1
A