・Current measurement parts
Eco-POWER METER measures the current as below.
System
Single-phase two-wire
Single-phase three-wire
Three-phase three-wire
Three-phase four-wire

6.2.4 Voltage

・It displays the voltage value of the load.
・Press <SHIFT/▽> to change voltage between P1 and P0, P2 and P0, P3 and P0.
*Before start measuring, select phase and wire system according to the measured load.
When Single-phase 3-wire or Three-phase 3-wire is selected, it doesn't measure Single-phase
2-wire system correctly. When Three-phase 4-wire system is selected, it doesn't measure
Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire system correctly.
Select phase and wire system according to the measured system.
(Refer to the explanation of setting mode.)
[V]
Lighting
・When input voltage is under 10.0V at 200V range, and when input voltage is under 20.0V at 400V
range, it displays "0.0" and doesn't measure.
・When input voltage exceeds 150%F.S. at each range, 「
・Voltage measurement parts
Eco-POWER METER measures the voltage as below.
System
Single-phase two-wire
Single-phase three-wire
Three-phase three-wire
Three-phase four-wire
Display
L1 (CT1)
L1-phase current
L1(R)-phase current
L1(R)-phase current
L1(R)-phase current
Display
L1V
Voltage
between P1 and P0
Voltage
between P1 and P0
Voltage
between P1 and P0
Voltage
between P1 and P0
L2 (CT2)
-
L2 (S)-phase current
L2 (T)-phase current
L2 (S)-phase current
L2V
---
Voltage
between P2 and P0
Voltage
between P2 and P0
Voltage
between P2 and P0
38
KW8M Eco-POWER METER
L3 (CT3)
-
-
-
L3 (T)-phase current
」 will be displayed.
L3V
---
---
---
Voltage
between P3 and P0