Low Voltage Directive - Panasonic KW1M-H User Manual

Eco-power meter
Table of Contents

Advertisement

Recommended Cable
Use the transmission cables shown below for Eco-POWER METER RS485 communication system.
Cable
Size
1.25 mm
(AWG16)
or more
Twisted-
pair
with shield
0.5 mm
(AWG20)
or more
0.75 mm
VCTF
(AWG18)
or more
Cable
Twisted-pair
with shield
Conductor
VCTF
Conductor

3.7 Low Voltage Directive

When using in the application confirming to EN61010-1/IEC61010-1, make sure to satisfy the following
conditions.
(1) Pulse output part secure only basic insulation. In order to secure reinforced (double) insulation
demanded by EN 61010-1/ IEC61010-1, secure basic insulation or more with load side and
reinforced (double) insulation with communication system side.
(2) Provide the voltage input part with an EN60947-1 or EN60947-3 compliant circuit breaker.
The breaker that connects to the voltage input part must arrange at the position easily reached,
and display shows it is the breaker of the equipment.
(3) Use a wire with basic insulation or more for a wire cramped (or connected) CT.
【Environmental conditions】
・Overvoltage category Ⅱ, Pollution degree 2
・Indoor use
・An ambient temperature of –10 to 50℃
・An ambient non-condensing humidity of 35 to 85%RH (at 20℃)
・Altitude of 2000m or less
【Mount the product in a place with】
・A minimum of dust, and an absence of corrosive gases
・No flammable, explosive gasses
・Few mechanical vibrations or shocks
・No exposure to direct sunlight
・No large capacity electromagnetic switches or cables through which large current is flowing
Conductor
Resistance
(at 20℃)
2
Max.16.8Ω/km
Polyethylene
2
Polyethylene
Max.33.4Ω/km
2
Max.25.1Ω/km
PVC
Section
Shield
Jacket
Jacket
Insulator
Material
Thickness
Max.
0.5 mm
Max.
0.5 mm
Max.
0.6 mm
Notes
1) Use shielded type twist cables.
2) Use only one type of the transmission cables.
2) Do not mix different types of the cables.
Insulator
3) Use twist pair cables under a bad noise
environment.
Insulator
11
KW1M-H Eco-POWER METER
Cable
Applicable cable
diameter
HITACHI
KPEV-S
Approx.
2
8.5 mm
1.25 mm
Belden Inc. 9860
HITACHI
KPEV-S
Approx.
2
×1P
7.8 mm
0.5 mm
Belden Inc. 9207
VCTF
Approx.
2
0.75 mm
6.6 mm
(JIS)
×1P
×2C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kw1m-h eco-power meterAkw1121

Table of Contents