Operating power supply
Measured voltage input
Do not ground the secondary side.
3.4 For Output connection
・Since the transistor output is insulated from the internal circuit by a photo-coupler, it can be used both
as a NPN output and PNP (equal value) output.
NPN output
Pulse (+)
3.5 RS485 Communication
・When using shielded cable for the RS485 transmission line, ground one end.
Use a class D dedicated earth for grounding. Do not share a ground with other earth lines. (Fig.1)
・Be sure to connect with daisy chain the RS485 transmission line between each unit.
Do not use a splitter. (Fig.2)
・With a terminal station, RS485 (E) (No.10) and RS485 (-) (No.9) should be shorted.
*E terminal is not SG (signal ground) terminal. Do not ground shielded cable.
(Fig.1)
To RS485 device
(Fig.2)
(Fig.B) No Good example
Insulated
Input equipment
transformer
(sensor etc.)
(+)
(-)
Eco-POWER
METER
Eco-POWER METER
Pulse (-)
6
7
Load
+
-
Power supply for Load
Eco-POWER METER
Shielded cable
Class D grounding
Correct wiring
○
Incorrect wiring
×
Operating power supply
Measured voltage input
Auto transformer
Eco-POWER
Do not use an auto-transformer.
PNP output
Pulse (+)
General station
(+)
(-) ( E )
Shielded cable
Terminal
station
10
KW8M Eco-POWER METER
Input equipment
(sensor etc.)
(+)
(-)
METER
Eco-POWER METER
Pulse (-)
6
7
Load
+
-
Power supply for Load
Eco-POWER METER
Terminal station
(+)
(-) ( E )
Shorted
Class D grounding
Terminal
station