Level 2 - Programming (Installer Level)

To access the second programming level press the
UP () and DOWN () keys and the LIGHT key
simultaneously for a few seconds.
When the first programming variable appears the
system automatically goes to stand-by.
1. Select the variable to be modified by pressing the
UP () and DOWN () keys.
When the parameter has been selected it is
possible to:
• view the setting by pressing the SET key.
• modify the setting by holding the SET key
down and pressing the () or () key.

List of Level 2 variables (Installer Level)

Variables
Explanation
AC
Door switch status
F3
Fan status with compressor off
F4
Fan pause during defrost
dE
Sensor presence
If the evaporator sensor is disabled defrosts are
carried out cyclically with period d0: defrosting
ends when an external device trips and closes the
remote defrost contact or when time d3 expires.
d1
Defrost type, cycle inversion (hot gas) or with
heater elements
Ad
Not to be used
Ald
Minimum and maximum temperature
signalling and alarm display delay
C1
Minimum time between shutdown and
subsequent switching on of the compressor.
CAL
Correction of sensor signal
Pc
Compressor protection contact status
doC
Compressor safety time for door switch: when
the door is opened, the evaporator fans shut down
and the compressor will continue working for time
doC, after which it will shut down.
Fst
Fan shutdown temperature
The fans will stop if the temperature value detected
by the evaporator sensor is higher than this value.
Fd
Fan differential below Fst
© Danfoss A/S (RA Marketing/MWA), Nov. 08
2. When the configuration settings have been
completed, exit the menu by pressing the
() and () keys simultaneously and keep
them pressed until the room temperature
reappears.
3. Changes are saved automatically when you exit
the configuration menu.
4. Press the STAND-BY key to enable electronic
control.
RS8FE102, 080R9278
Operation and Maintenance Guide
Value
0 = normally open
1 = normally closed
0 = fans run continuously
1 = fans only run when
compressor is working
0 = fans run during defrost
1 = fans do not run during defrost
0 = evaporator sensor present
1 = no evaporator sensor
1 = hot gas
0 = element
1 - 240 min
0 - 15 min
-10 - +10
0 = NO
1 = NC
0...5 minutes
-45 - +45°C
0 - +10K
Default
0
1
1
0
0
120 min
0 min
0
0 = NO
0
+45°C
2K